99
-
○
5
Frequency detection (set value=4)
This contact is "closed" when output frequency is equal to or less than Cn-32, as
shown in the figure below.
Output frequency
≦
Cn-32
Cn-32: Frequency detection 1 level
Cn-22: Agreed frequency detection width
○
6
Frequency detection (set value=5)
This contact is "closed" when output frequency is equal to or greater than Cn-33, as
shown in the figure below.
Output frequency
≧
Cn-33
Cn-33: Frequency detection 2 level
Cn-22: Agreed frequency detection width
○
7
Inverter operation ready (set value=6)
This is "closed" when the inverter has become ready for operation.
○
8
During undervoltage (UV) detection (set value=7)
This contact remains "closed" as long as the inverter is detecting undervoltage.
○
9
During baseblock (set value=8)
This contact is always "closed" when inverter output is shut OFF.
○
10
Frequency reference mode (set value=9)
This contact is "closed" when the frequency reference mode from the operator is
selected.
Cn-22
OUTPUT FREQUENCY
FREQUENCY
DETECTION SIGNAL
CLOSED
Cn-32
Cn-22
OUTPUT FREQUENCY
FREQUENCY
DETECTION SIGNAL
Cn-33
CLOSED