(5) Operation Mode Select 2 (Sn-05)
1st digit
Select processing to be performed when the STOP key of the digital operator is
depressed during running by control circuit terminals.
1st digit = 0
:
During running by signals from control circuit terminals, the STOP key
from the operator is accepted. If the STOP key is depressed, the
inverter stops according to the setting of the 3rd and 4th digits of Sn-04
while the STOP LED indicator blinks. This stop command is held within
the inverter until both the FWD run command and REV run command
of control circuit terminals become "open", or other frequency reference
is selected in the multi-step speed command or jog frequency
reference section.
1st digit = 1
:
During running by signals from control circuit terminals, the STOP key
from the operator is not accepted.
2nd digit
(REV run prohibited)
2nd digit = 0
:
REV run command from control circuit terminals or the digital operator
is accepted.
2nd digit = 1
:
REV run command from control circuit terminals or the digital operator
is not accepted.
3rd digit
(selection of double scanning of sequence command)
3rd digit = 0
:
Sequence command (control circuit terminals I to 8) is scanned twice.
3rd digit = 1
:
Sequence command (control circuit terminals I to 8) is scanned once.
4th digit(
key functions select
)
4th digit=0 : The digital operator key is JOG key function.
(the JOG key function is enabled under Local mode )
4th digit=1 : The digital operator key is used as Local/Remote (L/R) switch key.
D
At the Local mode, the inverter operates by frequency reference and
run command from digital operator.
D
At the Remote mode, if selected the multi-function contact input
(terminal
5
~
8
) as Local/Remote operation signal
(i.e. the set value of Sn-15~18 is 0 1)
1
if terminal
5
~
8
=”open”(Remote mode), the inverter operates
according to the setting of Sn-04 1
st ,2
nd digits and Sn-08 1
st ,
2
nd digits (i.e. the key used as Remote key function.)
2
if terminal
5
~
8
=”close”(Local mode), the inverter operates
by frequency reference and run command from digital operator.
(i.e. the Remote key function invalid).
∗
.The Local/Remote (L/R) key function is enabled only stopping.