64
-
2.4 System Parameters S n -
□ □
Function
Parameter
No.
Name
LCD Display
(English)
Description
Factory
Setting
Ref.
Page
Capacity
Setting
Sn-01
Inverter Capacity
Selection
Sn-01=29
440V 25HP
Inverter Capacity Selection
*1
69
70
V/f Curve
Sn-02
V/f Curve Selection
Sn-02=2
V/f Curve
V/f pattern Selection
2
71
Operator
Status
Sn-03 Operation
Status
Sn-03=0000
Operate Setting
0000
:
Setting and reading of An-
□□
, Bn-
□□
,Cn-
□□
, Sn-
□□
enabled
0101
:
Setting and reading of An-
□□
,
Readinng of Bn-
□□
,Cn-
□□
, Sn-
□□
enabled
1110
:
Contents Initialigation (2-wire)
*2
1111
:
Contents Initialigation (3-wire)
*2
1000
:
Initialize Un-11 contents
1001
:
Initialize Un-12 contents
0000 72
Sn-04
Operation Mode
Select 1
(RUN
.
STOP
Selection)
Sn-04=0011
Stopping Method
- - -0
:
Frequency Command = Control
circuit terminals VIN or AIN
- - -1
:
Frequency Command = Frequency
Command 1 (An-01)
- -0 -
:
RUN
.
STOP Command = Control
circuit terminals
- -1 -
:
RUN
.
STOP Command =
Digital Operator
00- -
:
Stopping method = Ramp to stop
01- -
:
Stopping method =Coasting
to stop
10- -
:
Stopping method =Full-range DC
injection branking stop
11- -
:
Stopping method = Coasting stop
(timer function provided)
0011
73
74
75
Sn-05
Operation Mode
Selection 2
(I/O terminal function
selection)
Sn-05=0000
I/O term. Fct
- - -0
:
Stop key effective during operation
from control terminal
- - -1
:
Stop key effective during operation
from control terminal
- -0 -
:
Reverse run enabled
- -1 -
:
Reverse run disabled
- 0- -
:
Control input terminals
○
1
~
○
8
are
scanned twice.
-1- -
:
Control input terminals
○
1
~
○
8
are
scanned once.
0 - - -
:
Digital operator key
= JOG key function
1- - -
:
Digital operator key
= L/R (Local/Remote) key function
0000
76
eration Mode
Select
Sn-06
Operation Mode
Selection 3
(S-curve and
frequency reference
characteristics)
Sn-06=0000
S-curve Cmd. Char.
- -00
:
S curve=0.2sec
- -01
:
S curve=0.0sec (NO S curve)
- -10
:
S curve=0.5sec
- -11
:
S curve=1.0sec
-0 - -
:
Reference command has forward
characteristics
(0-10V or 4-20mA/0~100%)
-1 - -
:
Reference command has reverse
characteristics
(0-10V or 4-20mA/100~0%)
0- - -
:
Stop by reference input when
frequency reference is missing
1- - -
:
Operation to continue with 80% of
frequence reference when
frequency reference is missing
0000
77
78
79
JOG
(L/R)
JOG
(L/R)
Summary of Contents for 7300PA series
Page 6: ... 4 PART I INSTALLATION MANUAL ...
Page 35: ... 33 PART II OPERATION MANUAL ...