102
-
(20) LCD Language displayed selection (Sn-25)
Sn-25 = 0
:
English
Sn-25 = 1
:
Chinese
(21) Multi-Function Analog Output A01 Function Selection (Sn-26)
(22) Multi-Function Analog Output A02 Function Selection (Sn-27)
The multi-function analog output A01 and A02 can be set to monitor the following 11
status items as shown below:
Description
Sn-26, Sn-27
Setting
Monitored Contents (LCD Display)
Input Output
0
Frequency Command
0 ~ max. frequency
1
Output Frequency
0 ~ max. frequency
2
Output Current
0 ~ rated Current
3
Output Voltage
0 ~ rated Voltage
4 DC
Voltage
220V: 0 ~ 400VDC
440V: 0 ~ 800VDC
5 Output
Power
0 ~ max. applicable motor
capacity
6
VIN Analog Command
0 ~ 10V
7
AIN Analog Command
4 – 20mA
8
AUX Analog Command
0 ~ 10V
9
PID detected value (VIN + AIN)
0 ~ 10V
10
Comm. Control
0 ~ 100%*
1
0 ~ 10V
The output gain Bn-11, Bn-12 will determine the output voltage at multi-function
analog output at A01 and A02 terminal. The specified multiple of 10V will correspond
to the 100% output monitored value.
*1
:
When Sn-26 ~ Sn-27=10, the multi-function output terminals A01, A02 are controlled
by RS-485 commutation. Please ref. To “7300PA MODBUS/PROFIBUS application
manual”.
(23) Not Used (Sn-28)
(24) Not Used (Sn-29)