55
-
(13) Frequency agree detection level (Cn-21)
Set an agreed frequency point in units of 0.1 Hz.
(14) Frequency agree detection width (Cn-22)
Set an agreed frequency detection width in units of 0.1 Hz. The relation with
multi-function contact output are shown in the four figures below (a) , (b)and the
frequency detection 1,2(Cn-32,Cn-33) in page 57 .
(a) Agreed frequency (set value of multi-function contact output Sn-20~22= 2)
This is "closed" when output frequency is within the detection width shown in the
following figure.
(Frequency ref.
-
Cn-22)
≦
Output frequency
≦
(Frequency ref.
+
Cn-22)
Cn-21: Agreed frequency point
Cn-22: Agreed frequency detection width
(b) Agreed frequency (set value of multi-function contact output Sn-20~22= 3)
This is "closed" when acceleration or deceleration is completed and output
frequency is within the detection width shown in the figure below.
(Cn-21
-
Cn-22)
≦
Output frequency
≦
(Cn-21
+
Cn-22)
Cn-21: Agreed frequency point
Cn-22: Agreed frequency detection width
DETECTION WIDTH Cn-22
FREQUENCY REF.
OUTPUT FREQUENCY
AGREED FREQUENCY
SIGNAL
CLOSED
DETECTION WIDTH Cn-22
FREQUENCY REF.
OUTPUT FREQUENCY
AGREED FREQUENCY
SIGNAL
CLOSED
Cn-21
Summary of Contents for 7300PA series
Page 6: ... 4 PART I INSTALLATION MANUAL ...
Page 35: ... 33 PART II OPERATION MANUAL ...