3.1.5 Using More Than One DRIVER
This section shows an example of the wiring and the precautions when more than one DRIVER is used.
(1) Wiring Example
Connect the alarm output (ALM) terminals for three DRIVERs in series to enable alarm detection relay 1RY to
operate. When the alarm occurs, the ALM output signal transistor is turned OFF.
(2) Precautions
Multiple DRIVERs can share a single molded-case circuit breaker (1QF) or noise filter. Always select a
molded-case circuit breaker or noise filter that has enough capacity for the total power supply capacity (load
conditions) of the DRIVERs.
DRIVER
DRIVER
DRIVER