4 Operation
4-15
(2) Stopping Method for Servomotor When an Alarm Occurs
There are two types of alarms (Gr.1 and Gr.2) that depend on the stopping method when an alarm
occurs. Select the stopping method for the servomotor when an alarm occurs using Pn001.0 and
Pn00B.1.
The stopping method for the servomotor for a Gr.1 alarm is set to Pn001.0.
The stopping method for the servomotor for a Gr.2 alarm is set to Pn00B.1.
Refer to the information on alarm stopping methods in
9.1.1 List of Alarms
.
- Stopping Method for Servomotor for Gr.1 Alarms
The stopping method of the servomotor when a Gr.1 alarm occurs is the same as that in
(1)
Stopping Method for Servomotor after SV_OFF Command is Received
.
Parameter
Stop Mode
Mode After Stop-
ping
When Enabled
Classification
Pn001
n.
口口口
0
[Factory setting]
DB
DB
After restart
Setup
n.
口口口
1
Coast
n.
口口口
2
Coast
Coast
- Stopping Method for Servomotor for Gr.2 Alarms
Parameter
Stop Mode
Mode After
Stopping
When
Enabled
Classifica-
tion
Pn00B
Pn001
n.
口口
0
口
[Factory setting]
n.
口口口
0
[Factory setting]
Zero-speed stop-
ping*
DB
After
restart
Setup
n.
口口口
1
Coast
n.
口口口
2
n.
口口
1
口
n.
口口口
0
[Factory setting]
DB
DB
n.
口口口
1
Coast
n.
口口口
2
Coast
∗
Zero-speed stopping: The speed reference is set to 0 to stop quickly.
Note: The setting of Pn00B.1 is effective for position control and speed control. Pn00B.1 will be ignored for torque control
and only the setting of Pn001.0 will be valid.
Summary of Contents for LECYU Series
Page 30: ...1 Outline 1 9 1 4 3 Three phase 200 V LECYU2 V9 Models ...
Page 65: ...3 Wiring and Connection 3 11 3 Wiring Example with DC Power Supply Input DRIVER ...
Page 92: ...3 Wiring and Connection 3 38 External Dimensions Units mm 1 FN Type by Schaffner EMC Inc ...
Page 93: ...3 Wiring and Connection 3 39 2 FN Type ...
Page 143: ...4 Operation 4 44 ...