4 Operation
4-31
4.6.2 External Torque Limit
Use this function to limit torque by inputting a signal from the host PC or PLC...etc at specific times during
machine operation. For example, some pressure must continually be applied (but not enough to damage the
workpiece) when the robot is holding a workpiece or when a device is stopping on contact.
(1) Input Signals
Use the following input signals to limit a torque by external torque limit.
Type
Signal
Name
Connector
Pin Number
Setting
Meaning
Limit value
Input
/P-CL
Must be allocated
ON
(closed)
Forward external torque limit ON
The smaller value of these set-
tings: Pn402 or Pn404
OFF
(open)
Forward external torque limit
OFF
Pn402
Input
/N-CL
Must be allocated
ON
(closed)
Reverse external torque limit ON
The smaller value of these set-
tings: Pn403 or Pn405
OFF
(open)
Reverse external torque limit
OFF
Pn403
Note: Use parameter Pn50B.2 and Pn50B.3 to allocate the /P-CL signal and the /N-CL signal for use. For
details, refer to
3.3.1 Input Signal Allocations
.
(2) Related Parameters
Set the following parameters for external torque limit.
Pn402
Forward Torque Limit
Speed
Position
Torque
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 800
1%
800
Immediately
Setup
Pn403
Reverse Torque Limit
Speed
Position
Torque
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 800
1%
800
Immediately
Setup
Pn404
Forward External Torque Limit
Speed
Position
Torque
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 800
1%
100
Immediately
Setup
Pn405
Reverse External Torque Limit
Speed
Position
Torque
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 800
1%
100
Immediately
Setup
The setting unit is a percentage of the rated torque.
Note: If the settings of Pn402, Pn403, Pn404, and Pn405 are too low, the torque may be insufficient for acceleration or
deceleration of the servomotor.
Summary of Contents for LECYU Series
Page 30: ...1 Outline 1 9 1 4 3 Three phase 200 V LECYU2 V9 Models ...
Page 65: ...3 Wiring and Connection 3 11 3 Wiring Example with DC Power Supply Input DRIVER ...
Page 92: ...3 Wiring and Connection 3 38 External Dimensions Units mm 1 FN Type by Schaffner EMC Inc ...
Page 93: ...3 Wiring and Connection 3 39 2 FN Type ...
Page 143: ...4 Operation 4 44 ...