5 Adjustments
5-13
5.2.2 Tuning-less Levels Setting (Fn200) Procedure
CAUTION
• To ensure safety, perform the tuning-less function in a state where the DRIVER can come
to an emergency stop at any time.
The procedure to use the tuning-less function is given below.
Operate the tuning-less function from the S.
(1) Preparation
Check the following settings before performing the tuning-less function. If the settings are not
correct, "NO- OP" will be displayed during the tuning-less function.
•
The tuning-less function must be enabled (Pn170.0 = 1).
•
The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
•
The test without a motor function must be disabled. (Pn00C.0 = 0).
(2) Operating Procedure with Sigma Win+
1. In the S
Σ
-V component main window, click
Setup
and then
Response Level
Setting
.
2. Click the setting arrows to adjust the response level so that the machine does not
vibrate.
The factory setting is 4, the maximum level.
3. Click
Completed
to save the setting in the DRIVER.