57 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Parameters
23.09.2010
Parameter – type [AnalogValueEnum] – that represents the backup value and
becomes valid in the following cases:
a change in status to 'MasterDown'
and
the parameter [BackupMode] = VALUE
Value range
Unit
0...10000 0.01
%
4.12.4 StartSynchronization
Parameter – type [SynchEnum] – for synchronization after a reset.
The synchronization cannot be interrupted. After a reset the current position of the
stroke model is set to 0 % before the synchronization is started.
Possible values
Description
NONE No
synchronization
SINGLEOPEN
Immediate opening synchronization for 1.5
[rise time]
SINGLECLOSE
Immediate closing synchronization for 1.5
[fall time]
4.12.5 LimitSynchronization
Parameter for stopping a drive at specified end positions. In doing so, [StrkPos] is
set to [AOValue] at the same time.
While [LmStp]=TRUE,
all synchronization types remain irrelevant
any ongoing synchronization operation is cancelled
If the local override function is active, [LmStp] is set to FALSE.
Note
The function becomes even more useful if an end position detection function is
available with an additional input and a correspondingly assigned end switch.
Possible values
Description
Selected No
synchronization
Not selected
Stop
4.12.6 StartSynchronization
Parameter for starting the synchronization.
StartSynchronisation is automatically triggered after a reset if this has been
specified accordingly.
The synchronization is not interrupted by any other event.
Possible values
Description
NONE No
synchronization
SINGLEOPEN
Immediate 'Open' synchronization for 1.5
[rise time]
SINGLECLOSE
Immediate 'Close' synchronization for 1.5
[fall time]
Definition,
addition
Definition,
addition
Definition,
addition
Definition,
addition