14 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Engineering
23.09.2010
3 Engineering
Engineering is based on the GSDML file. It is standardized in accordance with the
GSDML Specification for Profinet IO V2.2.
The engineering tool (Simatic Manager) is part of the engineering process. It needs
to be informed by an import about which GSDML file to use for the Profinet BIM.
As a result of the import, the Profinet BIM will then appear as a field device in the
hardware catalog of the program (path: ...\Profinet IO\I/O\TX-I/O).
Engineering can be carried out in the following two different ways:
1
a) First, the application is created and loaded into the CPU and
b) then the periphery is configured,
or
2
a) First, the modules are configured and tested, and
b) then the application is loaded.
In this case, specific organization blocks (OBs) must be available. If one of
these organization blocks is missing, then in the event of
configuration errors
and
if a
module fails during running operation
the
CPU
will be stopped.
The following organization modules should be available:
OB no
OB name
Meaning
OB82
I/O Point Fault 1
Diagnostics alarm
OB83
I/O Point Fault 2
Removal/insertion (of modules)
OB85
OB Not Loaded Fault
Program operation error
OB86
Loss of Rack Fault
Module rack failure
OB122
Module Access Error
Program operation error
can be found in the online help function of the SIMATIC Manager
If no organization blocks are yet available, you can find information as follows:
SIMATIC Manager
>
Help
>
Find
tab >
Organization blocks
or
SIMATIC Manager
>
Wizard for new project
>
Next
>
Select CPU type
>
Next
> mark the required OB >
Help for OB
button
Note
In this sequence do
not
click the
Finish
button.
We assume in this manual that are beginning a project from the very start. The
following procedure is useful:
1. SIMATIC
Manager
Create a
Step7
project
Step7
project
2.
Import Profinet BIM GSDML file
Current GSDML file: GSDML-V2.2-Siemens-ProfinetBim-<yyyymmdd>.xml
Refer to Section 3.2 –
Instal GSDML file:
Import GSDML and BMP files
3.
Under HW Config on the programming PC: engineer S7-CPU 2xx/3xx/4xx-
2PN/DP
The corresponding step-by-step method is given below.
GSDML file
SIMATIC Manager
Workflow
Help regarding the
organization blocks
(OBs)
Procedure