18 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Engineering
23.09.2010
6.
Import Profinet BIM
to the Profinet network by drag&drop of the
TXB1.Profinet BIM.
After releasing the mouse button, the Profinet BIM is inserted and is displayed
in the Profinet network.
Note
When clicking the Profinet BIM, the slot allocation and I/O addresses are
displayed in detail in the station window.
7. Rightclick
I/O bar
> context menu: Object Properties
Opens the PROFINET I/O system properties dialog field.
8.
Update time
tab: mark the device >
Edit
button
Opens the Edit update time/mode dialog field.
9. Set
the
update time
to
256 ms
using the dropdown list box.
This is a recommendation. A higher clock rate makes no sense since the
island bus is clocked at 512 ms.
10. Close
with
OK.
3.3
Engineering the Profinet BIM with the
SIMATIC Manager
The Profinet BIM is a modular device. It supports specific TX-I/O modules and their
corresponding channel functions.
TXM1.8D TXM1.8U TXM1.8X TXM1.6R
TXM1.6RL
TXM1.16D TXM1.8U-ML
TXM1.8X-ML TXM1.6R-M TXM1.8P
The following sections explain the engineering procedure in terms of
module configuration
submodule configuration and
parameterization.
Profinet BIM supports 120 slots. TX-I/O modules can be inserted in any slot
within this range (1...120).
Supported TX-I/O
modules
Supported slots