64 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
Diagnostics
23.09.2010
5.2
Diagnostics on Profinet BIM
LED indication
Description
Run
FL
T
Link1
Com
m
1
Link2
Com
m
2
Cause
on
off
Firmware
runs
without
faults
on
flashing
Alarm
present
on
on
Firmware is running, no Profinet
communication
flashing flashing
Hardware
problem
flashing off
Firmware update is running, firmware is
running
flashing on
Firmware update is running, firmware is
not running
off
on
Firmware is not running
on
Connection to Ethernet port 1 available
on
Connection to Ethernet port 2 available
flickerin
g
Ethernet communication on port 1
flickerin
g
Ethernet communication on port 2
5.3
Diagnostics in Telnet
5.3.1
Telnet Commands
The following commands are used on the DOS command level for working with
Telnet:
help firmware
Command
Description
fwupdate
Starts firmware update
cimiupdate
Starts CIMI firmware update
cfgget
Get device configuration
cfgupdate
Update device configuration
calibrate
Starts CIMI calibration
devicestop
Stops Profinet IO Device
devicestart
Starts Profinet IO Device
setPvMode
Sets ComMode of a device
to Master/Slave or Frontend/Backend
help info
Command
Description
devicelist
Shows the device and module list
alarmlist
Shows the active alarms
diagbasic
Display the diagnostic and process
alarms
diagextended
Display the extended diagnosis
ethstats
Display the ethernet statistics
showlog
Display trace log
version
Display the firmware version