9 / 94
Siemens
TX-I/O PROFINET BIM V1.0
CM110564en_02
Building Technologies
General
23.09.2010
2 General
2.1
Overview
Profinet BIM is an interface module which enables to access from the Simatic
infrastructure to
process data
configuration data and
parameters
of TX-I/O modules.
2.2
Application
The purpose of Profinet BIM is to connect the two communication media, TX-I/O
and PROFINET-DP, and in this way to allow access to the DESIGO I/O modules
from a SIMATIC S7.
Within SIMATIC
Profinet BIM is handled as a Profinet I/O device and
TX-I/O modules are represented as Profinet I/O modules.
In the Profinet infrastructure, Profinet BIM behaves as a PNIO device and
supports the datagram data exchange in the direction of the Profinet IO
controller (SIMATIC S7).
On the island bus (communication bus of the TX-I/O modules) the Profinet BIM
operates as the island bus master. Consequently, it is responsible for the data
flow to and from the TX-I/O modules.
All data forwarded via the Profinet BIM is converted to the datagram format used
by SIMATIC S7.
Engineering of the Profinet BIM is carried out using standard Profinet I/O
engineering methods. The properties of the TX-I/O modules are saved in the
product-specific GSDML file. The GSDML file provides the basis for engineering
with the Profinet project engineering tool (e.g., Simatic Manager).
The Profinet BIM does not require engineering. It receives its parameters from the
Profinet I/O controller assigned to it (e.g., from the SIMATIC S7).
Function
Handling
Behavior
Engineering