Preface
viii
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155
Page 1: ...Edition 08 2020 Operating Instructions SITRANS L Radar Transmitters SITRANS LR150 https www siemens com ...
Page 2: ... 4 Connecting 5 Access protection 6 Setup with the integrated HMI 7 Setup with smart device Bluetooth 8 Setup with PC notebook HART modem 9 Operating 10 Setup with SIMATIC PDM EDD 11 Diagnostics and troubleshooting 12 Service and maintenance 13 Certificates and approvals 14 Technical data and dimensions 15 08 2020 A5E50352155 62711 76 01 ...
Page 3: ...ied personnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper Use of Siemens Products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufact...
Page 4: ...mation 4 3 Description 7 3 1 Configuration 7 3 2 Principle of operation 8 3 3 Adjustment 9 3 4 Packaging transport and storage 10 4 Installing mounting 13 4 1 General instructions 13 4 2 Mounting instructions 13 4 3 Measurement setup Flow 17 5 Connecting 19 5 1 Preparing the connection 19 5 2 Connecting 20 5 3 Wiring plan 21 5 4 Connecting HMI to electronic module 22 5 5 Switch on phase 22 6 Acces...
Page 5: ...ngs 47 7 7 1 Selection HART variable 47 7 7 2 Transmitter 48 7 7 3 Adjustment 48 7 7 4 Current output 49 7 7 5 Volume 50 7 7 6 Volume flow 52 7 7 7 Custom 53 7 7 8 Display 54 7 8 Maintenance and diagnostics 55 7 8 1 Signal 55 7 8 2 Peak values 57 7 8 3 Circuit test 58 7 8 4 Resets 59 7 8 5 Frequency 60 7 9 Communication 61 7 9 1 HART address 61 7 10 Safety 61 7 10 1 user PIN 61 7 10 2 Bluetooth PI...
Page 6: ... 84 12 7 Technical support 85 12 8 How to proceed if a repair is necessary 86 13 Service and maintenance 87 13 1 Dismounting steps 87 13 2 Disposal 87 14 Certificates and approvals 89 14 1 Radio licenses 89 14 2 EU conformity 89 15 Technical data and dimensions 91 15 1 Technical data 91 15 2 Dimensions 95 15 3 Licensing information for open source software 96 15 4 Trademark 96 SITRANS LR150 Operat...
Page 7: ...Table of Contents vi SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 8: ...e Ex specific safety instructions for Ex applications These instructions are attached as documents to each transmitter with Ex approval and are part of the operating instructions Editing status 2020 08 03 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 vii ...
Page 9: ...Preface viii SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 10: ... implemented 1 3 Symbols used Information note tip This symbol indicates helpful additional information and tips for successful work Note This symbol indicates notes to prevent failures malfunctions damage to devices or plants Caution Non observance of the information marked with this symbol may result in personal injury Warning Non observance of the information marked with this symbol may result ...
Page 11: ...e of actions Numbers set in front indicate successive steps in a procedure Battery disposal This symbol indicates special information about the disposal of batteries and accumulators 2 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 12: ...y and persons or environmental contamination can result Also the protective characteristics of the transmitter can be impaired 2 4 General safety instructions This is a state of the art transmitter complying with all prevailing regulations and directives The transmitter must only be operated in a technically flawless and reliable condition The operator is responsible for the trouble free operation...
Page 13: ...ation of the regulations of the radio approvals of the respective country Further information can be found in the document Regulations for radar level measuring transmitters with radio licenses on our homepage 2 6 Installation and operation in the USA and Canada This information is only valid for USA and Canada Hence the following text is only available in the English language Installations in the...
Page 14: ...measures that may be implemented please visit https www siemens com industrialsecurity Siemens products and solutions undergo continous development to make them more secure Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used Use of product versions that are no longer supported and failure to apply the latest updat...
Page 15: ...Safety notes 2 7 Security information 6 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 16: ...PUK The further scope of delivery encompasses Documentation Ex specific Safety instructions with Ex versions If necessary further certificates Note Optional transmitter features are also described in this operating instructions manual The respective scope of delivery results from the order specification Scope of this operating instructions This operating instructions manual applies to the followin...
Page 17: ...t important data for identification and use of the transmitter 1 Transmitter type 2 Serial number 3 Technical data 4 Field for approvals 5 QR code for device documentation 6 Wireless access via smart device Figure 3 2 Layout of the nameplate example 3 2 Principle of operation Application area SITRANS LR150 is a radar transmitter for non contact continuous level measurement It is suitable for liqui...
Page 18: ...t On site adjustment of the device is carried out via the optionally integrated HMI Wireless adjustment Devices with integrated Bluetooth module can be adjusted wirelessly via Siemens mobile IQ app 1 Transmitter 2 Smart device Figure 3 3 Wireless connection to standard operating devices with integrated Bluetooth LE Adjustment via the signal cable Devices with signal output 4 20 mA HART can also be...
Page 19: ...ions PE foam or PE foil is also used Dispose of the packaging material via specialised recycling companies Transport Transport must be carried out in due consideration of the notes on the transport packaging Nonobservance of these instructions can cause damage to the device Transport inspection The delivery must be checked for completeness and possible transit damage immediately at receipt Ascerta...
Page 20: ... in the open Dry and dust free Not exposed to corrosive media Protected against solar radiation Avoiding mechanical shock and vibration Storage and transport temperature Storage and transport temperature see chapter Supplement Technical data Ambient conditions Relative humidity 20 85 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 11 ...
Page 21: ...Description 3 4 Packaging transport and storage 12 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 22: ... operating instructions or on the nameplate Hence make sure before mounting that all parts of the transmitter exposed to the process are suitable for the existing process conditions These are mainly Active measuring component Process fitting Process seal Process conditions in particular are Process pressure Process temperature Chemical properties of the medium Abrasion and mechanical influences 4 ...
Page 23: ...or the min max adjustment see following diagram 1 Reference point Figure 4 2 Reference point Installation position When mounting the device keep a distance of at least 200 mm 7 874 in from the vessel wall If the device is installed in the center of dished or round vessel tops multiple echoes can arise However these can be suppressed by an appropriate adjustment see chapter Set up If you cannot mai...
Page 24: ...4 4 Mounting of the radar transmitter on vessels with conical bottom Inflowing medium Do not mount the transmitters in or above the filling stream Make sure that you detect the medium surface not the inflowing product Figure 4 5 Mounting of the radar transmitter with inflowing medium Threaded nozzle und nozzle piece With threaded connection the antenna end should protrude at least 5 mm 0 2 in out ...
Page 25: ...dimensions also longer nozzles are possible however the local conditions must be taken into account Figure 4 7 Nozzle mounting Nozzle diameter d Nozzle length h 40 mm 1 150 mm 5 9 in 50 mm 2 200 mm 7 9 in 80 mm 3 300 mm 11 8 in 100 mm 4 400 mm 15 8 in 150 mm 6 600 mm 23 6 in Note When mounting on longer nozzles we recommend carrying out an auto false echo suppression see chapter Parameter adjustme...
Page 26: ...t errors you should use transmitters with guided radar 4 3 Measurement setup Flow In general the following must be observed while mounting the device Mounting the transmitter on the upstream or inlet side Installation in the centre of the flume and vertical to the liquid surface Distance to the overfall orifice or Venturi flume Min distance to the max height of damming for optimum accuracy 250 mm ...
Page 27: ...from tailwater Figure 4 10 Flow measurement with rectangular flume hmax max filling of the rectangular flume Khafagi Venturi flume 1 Position transmitter 2 Venturi flume Figure 4 11 Flow measurement with Khafagi Venturi flume hmax max filling of the flume B tightest constriction in the flume 18 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 28: ...th suitable internal or external limitation of the output current Keep in mind the following additional factors that influence the operating voltage Lower output voltage of the power supply unit under nominal load e g with a transmitter current of 20 5 mA or 22 mA in case of fault Influence of additional transmitters in the circuit see load values in chapter Technical data Connection cable Use cab...
Page 29: ...hread the cable gland is screwed in at the factory It is sealed with plastic plugs as transport protection You have to remove this plug before electrical connection NPT thread In the case of transmitter housings with self sealing NPT threads it is not possible to have the cable entry screwed in at the factory The cable gland is therefore covered with a red dust protection cap as transport protecti...
Page 30: ...e actuator lever away from the terminal opening When released the terminals are closed again Figure 5 1 Connection You can find further information on the max wire cross section under Technical data Electromechanical data Connecting Connect the transmitter according to the following wiring plan 5 3 Wiring plan Electronics and connection compartment 1 Voltage supply signal output SITRANS LR150 Oper...
Page 31: ...50 5 4 Connecting HMI to electronic module 5 5 Switch on phase After connection to the power supply the device carries out a self test Internal check of the electronics Output signal is set to failure The current measured value is then output on the signal cable 22 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 32: ...ime increases with each additional incorrect entry The Bluetooth PUK enables Bluetooth communication to be established in the event that the Bluetooth PIN is no longer known It can t be changed The Bluetooth PUK can be found in information sheet Device Bluetooth and Parameter Access Codes If this document is lost the Bluetooth PUK can be retrieved from your personal contact person after legitimati...
Page 33: ...nged The Device Access PUK can also be found on the supplied information sheet Device Bluetooth and Parameter Access Codes If this document is lost the Device Access PUK can be retrieved from your personal contact person after legitimation The storage and transmission of the user PIN is always encrypted SHA 256 algorithm 24 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 34: ...ustment elements 1 HMI 2 Adjustment keys Figure 7 1 Elements of the integrated display and adjustment unit Key functions Key Function All views return to the measured value view Editing view Selecting the parameter settings Editing view return to the parameter view without changing the parameter setting Measured value view Select the desired measured value Parameter view Select parameter Editing v...
Page 35: ...ective key is pushed the scrolling speed or the parameter change rate increases 10 minutes after the last key is pressed an automatic return to the measured value view is triggered Parameter changes that have not yet been confirmed are lost 7 2 Structure and views of the display Structure of the display 1 Title line 2 Main line 3 UP DOWN navigation arrows 4 INFO field 5 Locking symbol 6 EDIT indic...
Page 36: ...y Measured value view The measured value view shows the current measured values of the device as well as status and diagnostic messages Process value name and unit are displayed alternately 1 Process value name 2 Process value unit 3 Process value If the process value is too large to be shown on the display value has more than 5 digits hashes will be shown instead 4 Process value number 5 Diagnosi...
Page 37: ...e parameters parameter values and the wizards of the device 1 Parameter name 2 Parameter value 3 Parameter number 4 EDIT symbol permanently activated Figure 7 4 Parameter view Editing view Parameter values can be changed in this view Wizards are available for certain parameters Note While the device is in the editing view the output remains active and continues to respond to changes 1 Parameter na...
Page 38: ...urge bin MATERIAL TYPE SOLID OPEN Heap pile SILO UNITS DeviceUnits Physical Value Unit mm m in ft m LOWER CAL PT Level Adjustment Data 15 m UPPER CAL PT Level Adjustment Data 0 m COMMISSION CONFIRM OPERATION SPACE STRGE Vessel PRCSS Process vessel with agitation WTWLL Wet well PLSTC Outside of Plastic Tank OPEN Level of open liquid MATERIAL TYPE LIQUID DEMO Demonstration STRGE SILO Silo BIN Buffer...
Page 39: ... Horizontal cylindrical vessel VESSEL SHAPE CUSTM User programmable LINR VESSEL DIM A Linearization Curve Intermediate Height 0 mm LOWER CAL PT Level Adjustment Data 15 m UPPER CAL PT Level Adjustment Data 0 m VOL UNITS Level Scaling Scaling Unit Liter SCALE FORMAT Level Scaling Decimal Places Display 0 COMMISSION UPPER RANGE Level Scaling Max Scaled Value 100 OPERATION VFLOW MATERIAL TYPE LIQUID ...
Page 40: ...e LINR Linear CYLIN Horizontal cylindrical vessel VENTU Venturi trapezoidal weir rectangle weir PALM Flow Palmer Bowlus flume V NOT Flow VNotch triangle weir CONIC Conical Bottom SELECT OUTPUT LINEARIZTYPE Linearization Curve Type FLAT Inclined Bottom Linear SENSOR UNITS Device Units Physical Value Unit mm m in ft m LOWER CAL PT Level Adjustment Data 15 m UPPER CAL PT Level Adjustment Data 0 m CAL...
Page 41: ... min l h MI d m 3 s m 3 min m 3 h m 3 d lb s lb min lb h gal s gal min gal h gal d Mgal d ft 3 s ft 3 min ft 3 h ft 3 d bbl s bbl min bbl h bbl d ImpGal s ImpGal min Imp Gal h ImpGal d l s SCALE FORMAT Level Scaling Decimal Places Display 0 VOLUME FLOW UPPER SCALNG Level Scaling Max Scaled Value 100 l s UPPER SCALNG Level Scaling Max Scaled Value 100 l CUSTOM CUSTOM CURVE Linearization Points Leve...
Page 42: ...er Min Max Level Distance Reset Action Both values RESETS RESET PEAK STEMP Reset User Min Max Electronic Temperature Reset Action Both values NO FREQUENCY 1 EU Albania Andorra Azerbaijan Australia Belarus Bosnia and Herzegovina Canada Iceland United Kingdom Liechtenstein Moldova Monaco Montenegro New Zealand Northern Macedonia Norway San Marino Saudi Arabia Switzerland Serbia Turkey Ukraine USA 2 ...
Page 43: ... Press for configuration The symbol EDIT flashes 4 Use and to increase or decrease the value Press and hold the button to increase the scroll speed 5 To cancel without saving your changes press to return to the parameter view 6 Press to confirm the new value The display returns to the parameter view the EDIT symbol is permanently displayed and shows the new selection Check that the value is correc...
Page 44: ...application 4 Select Yes to confirm all parameter changes as the final step in the Quick Commissioning Wizard and return to the parameter view The main line of the display shows DONE 5 Press the key three times to return to the measured value view Note A reset to factory settings should be carried out before starting the Quick Commissioning Wizard if the device was previously used in another appli...
Page 45: ...e 3 Upper calibration point 4 Transmitter reference point 5 Lower calibration point 6 Level Figure 7 6 Overview quick setup level ullage distance user specific Setting Description Reference point LEVEL Material height Lower calibration point zero point of the process SPACE Distance from the Upper calibration point to the material surface Upper calibration point full point of the process DIST Dista...
Page 46: ...Unit UNITS Sets the measuring unit used default setting in brackets Meter m 3 decimal places Centimeter cm 1 decimal place Feet ft 3 decimal places Inches in 2 decimal places Lower calibration point LOWER CAL PT Sets the distance from the transmitter reference point to the lower calibration point usually corresponds to the zero point of the process Upper calibration point UPPER CAL PT Sets the dis...
Page 47: ...red again when the wizard is run again 7 5 3 Quick setup volume Mode OPERATION Sets the mode of operation that determines the output and display Setting Description LEVEL Level SPACE Space DIST Distance VOL Volume VFLOW Volume flow 1 Distance 2 Space 3 Upper calibration point 4 Transmitter reference point 5 Lower calibration point 38 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 48: ... WTWLL Wet well PLSTC Outside of Plastic Tank OPEN Level of open liquid LIQUID DEMO MODE Demonstration SILO Silo BIN Buffer surge bin MATERIAL TYPE SOLID OPEN Heap pile Unit UNITS Sets the measuring unit used default setting in brackets Meter m 3 decimal places Centimeter cm 1 decimal place Feet ft 3 decimal places Inches in 2 decimal places Vessel shape VESSEL SHAPE Sets the vessel shape and allo...
Page 49: ...libration point usually corresponds to the zero point of the process Upper calibration point UPPER CAL PT Sets the distance from the transmitter reference point to the upper calibration point usually corresponds to the full level Volume unit VOL UNITS Sets the measuring units for the volume Litre l Hectolitre hl Cubic meters m 3 Cubic inches in 3 Gallons gal Cubic foot ft 3 Barrel bbl Confirm CONF...
Page 50: ...e mode of operation that determines the output and display Setting Description Level LEVEL Space SPACE Distance DIST Volume VOL Volume flow VFLOW 1 Transmitter reference point 2 Upper calibration point 3 Lower calibration point 4 Far range 5 Zero level head 6 Level head 7 Material surface 8 Upper scaling point max volume flow Figure 7 8 Overview quick setup volume flow SITRANS LR150 Operating Inst...
Page 51: ...NITS Sets the measuring unit used default setting in brackets Meter m 3 decimal places Centimeter cm 1 decimal place Feet ft 3 decimal places Inches in 2 decimal places Measuring structure PRIM MEASDEV Sets the version of the measuring structure used Palmer Bowlus flume PBFLM Flow Venturi trapezoidal weir rectangle weir RWRC Flow VNotch triangle weir TPVWR User programmable USER Lower calibration ...
Page 52: ...es per minute m 3 min Cubic metres per hour m 3 h Cubic metres per day m 3 d lbs per second lb s lbs per minute lb min lbs per hour lb h US gallons per minute gal min US gallons per hour gal h US gallons per day gal d US mega gallons per day Mgal d Cubic feet per second Ft 3 s Cubic feet per minute Ft 3 min Cubic feet per hour Ft 3 h Cubic feet per day Ft 3 d Barrel per second bbl s Barrel per min...
Page 53: ...ed and settings are applied Setting No The wizard is closed and settings are not applied They must be entered again when the wizard is run again 7 5 5 Quick setup auto false echo suppression Use Used to prevent the detection of false echoes in a specified range Use the AFES wizard if there are known installations in the application and if false echoes are to be expected Notes If possible set the a...
Page 54: ...itator whisk is available it should be in operation As soon as the wizard is successfully completed parameter Auto false echo suppression is set to Activated and the determined TVT curve is used CONFIRM Accepts the settings as the last step in the wizard Setting Yes The wizard is closed and settings are applied Setting No The wizard is closed and settings are not applied They must be entered again...
Page 55: ...t of the process 7 6 2 Application example volume flow In this example a 12 inch 0 305 m venturi flume is installed in an open channel According to the manufacturer s data sheet the maximum nominal flow rate of the device is 1143 m 3 per hour at a maximum level of 0 6 m The SITRANS LR150 was installed at a height of 1 6 m above the channel 1 Transmitter 2 2 3 of the dimension of the converging 3 M...
Page 56: ...pper calibration point 1 Distance to maximum level Sets the Measurement end Volume flow unit VFLOW UNITS Setting according to the requirements of the end user Unit SCALE FORMAT Unit which corresponds to the level head Measurement end UPPER SCALNG To be taken from the data sheet of the manufacturer of the measuring structure 7 7 Settings 7 7 1 Selection HART variable Secondary value Sets a process ...
Page 57: ...ets the measuring unit used Setting Selection Selection Description mm Millimetre m Meter in Inch Transmitter UNITS ft Feet 7 7 3 Adjustment Lower calibration point LOWER CAL POINT Sets the distance from the transmitter reference point to the lower calibration point Upper calibration point UPPER CAL POINT Sets the distance from the transmitter reference point to the upper calibration point 48 SITR...
Page 58: ...s the damping filtering of the PV to smooth sudden fluctuations in measured values An increase in damping increases the reaction time of the device and affects the digital value and loop current For noisy output values increase parameter Damping value For faster reaction times reduce parameter Damping value Determine a value that meets the requirements for signal stability and reaction time The pr...
Page 59: ...put in case of an error Setting Selection Selection Description 3 6 mA CURRENT OUT FAULT CUR 21 mA Safety function with echo loss Defines the behavior of the safety function in case of echo loss and expiration of the LOE timer This defines which current value is output in case of echo loss Setting Selection Selection Description HOLD Last valid measured value CURRENT OUT FAILSAFE LOE FAULT Value a...
Page 60: ...ottom Upper scaling point vessel dimension A CYLIN Cylindrical vessel Upper scaling point VOLUME VESSEL SHAPE CUSTM Custom Vessel dimension A VESSSEL DIM A Adjusts the height of the vessel bottom in case of a conical parabolic spherical or flat sloping bottom Sets the height of the end piece for a horizontal tank with parabolic ends Volume unit Sets the measuring units for the volume Setting Selec...
Page 61: ...upper calibration point Measuring structure Sets the version of the measuring structure used Setting Selection Selection Description Other required parameters PBFLM Palmer Bowlus flume RWRC Venturi flume trapezoidal weir rectangular overfall TPVWR V Notch triangular weir VOLUME FLOW FLUME TYPE CUSTM Custom Flow unit Sets the measurement units for the volume flow Setting Selection Selection Descrip...
Page 62: ...te If the parameter Measurement end is set in the Quick commissioning wizard parameter Upper scaling point is automatically set to the same value If the value for one of these parameters is set outside the wizard the other value is not automatically adjusted Custom specific characteristics CUSTOM CURVE Is used to enter the index markers level and output for universal measuring structures If the ve...
Page 63: ...ctronics temperature STEMP a If the mode of operation is set accordingly b If the mode of operation is set accordingly Note If the parameter Operation is set in the wizard the value is automatically written to the parameter Start view If the parameter Start view or PV selector is changed after the wizard has been executed the last change is valid The options Volume Volume flow and Custom are only ...
Page 64: ... SIG STR Echo signal strength SIGNAL SIG QUALITY NOISE AVG Noise average value Echo configuration Near range Sets minimum distance from transmitter reference point beyond which an echo should be considered valid This is sometimes referred to as blanking or a blanking distance When the begin of the measuring range is activated the mm value is edited by pressing the key Setting Selection Selection D...
Page 65: ...lication is damped by using the values in the parameters Damping value and Transmitter damping value All other process values which are not preset or selected as main PV are only damped by the value in parameter Transmitter damping value Setting Selection Selection Description SIGNAL FILTERING REFORM ECHO Echo merging enabled TVT configuration Defines the threshold curve below which all echoes are...
Page 66: ...se echo suppression sets the end point of the determined TVT distance Determine the effective range of the automatic false echo suppression by measuring the actual distance from the transmitter reference point to the material surface Use a cable or measuring tape Setting Selection Selection Description HOVER LEVEL dB value of the basic noise AFES ON Activates the automatic auto false echo suppress...
Page 67: ...ature Maximum electronics temperature TR TEMP MAX Displays the value of the maximum transmitter temperature 7 8 3 Circuit test Simulation current output LOOP TEST A simulated value can be set to test the operation and mA connections during setup or maintenance of the unit Note The simulated value of the current output influences the output to the control system Press the key to stop and terminate ...
Page 68: ...e User PIN write protection is not reset Peak values are not reset Automatic false echo suppression is reset to the default setting deactivated but the detected TVT is not lost User specific TVT setting is reset to the default setting deactivated but User specific TVT index markers are not lost Selecting the Restore ordered configuration option restores the device settings ordered by the customer ...
Page 69: ...ada Liechtenstein Moldavia Monaco Montenegro New Zealand Northern Macedonia Norway San Marino Saudi Arabia Serbia Switzerland Turkey Ukraine United Kingdom USA Frequency 2 South Korea Taiwan Thailand Frequency 3 South Africa Frequency 4 Russia Depending on the frequency the metrological properties of the device can change see chapter Technical data input variable Further information can be found i...
Page 70: ...f the setting for parameter User PIN does not take effect immediately After changing the setting the device must be restarted or ten 10 minutes must elapse before the change takes effect Setting Selection Selection Description ACTIVT Activate User PIN Display OK USER PIN USER PIN CANCL Deactivate User PIN Display ENABL 7 10 2 Bluetooth PIN BLUETOOTH PIN In this menu item you can change the factory...
Page 71: ... 10 2 Bluetooth PIN is changed by the user and is no longer available access is only possible via the emergency Bluetooth unlock code on the information sheet also supplied 62 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 72: ...ct authentication each subsequent connection is made without a new authentication query Enter Bluetooth access code For authentication enter the 6 digit Bluetooth PIN in the next menu window You can find the code on the information sheet Device Bluetooth and Parameter Access Codes in the device packaging Note If an incorrect code is entered the code can only be entered again after a delay time Thi...
Page 73: ...Setup with smart device Bluetooth 8 1 Connecting 64 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 74: ...1 Saving the parameterisation data We recommend documenting or saving the parameterisation data via SIMATIC PDM That way the data are available for multiple use or service purposes SITRANS LR150 Operating Instructions 08 2020 A5E50352155 65 ...
Page 75: ...Setup with PC notebook HART modem 9 1 Saving the parameterisation data 66 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 76: ...om the App store to your mobile device 2 Launch the app Devices in range will appear 3 Click on the device you wish to connect to On first connection a PIN code shipped with the device needs to be entered see Device Bluetooth and SITRANS LR150 Operating Instructions 08 2020 A5E50352155 67 ...
Page 77: ...Operating Parameter Access Codes sheet Following successful PIN entry the device cockpit will be shown 68 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 78: ...Operating 4 Use the Setup Quick Commissioning to configure the transmitter for your application type SITRANS LR150 Operating Instructions 08 2020 A5E50352155 69 ...
Page 79: ...Operating Many diagnostic tools are supported including the echo profile viewer 70 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 80: ...u have the latest version of SIMATIC PDM the most recent Service Pack SP and the most recent hot fix HF Go to Software downloads http www siemens com processinstrumentation downloads In the product tree navigate to Automation Technology Process Control Systems SIMATIC PCS 7 System Components Plant Device Management SIMATIC PDM Start Proceed as follows 1 Launch SIMATIC PDM connect to device and upl...
Page 81: ...fline The status fields are cleared Figure 11 1 PDM structure view EDD offline start Figure 11 2 PDM structure view EDD offline continuation Procedure Select Device Wizard Quick Start to perform the initial commissioning Follow the guided commissioning steps according to your specific application 72 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 82: ... Select the curves to be loaded into the echo profile view then select Load selected curves Curves and other diagnostic information will be loaded after approximately 45 seconds 1 Blue line echo profile 2 Red line TVT 3 Brown line auto false echo suppression if active Figure 11 4 PDM echo profile view SITRANS LR150 Operating Instructions 08 2020 A5E50352155 73 ...
Page 83: ...rom the device menu and enter the distance to the material surface SIMATIC PDM supports many other useful features extensive diagnostic support and asset management Details are found in the SIMATIC PDM manual here https support industry siemens com cs ww en view 109755005 74 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 84: ...The cleaning helps that the nameplate and markings on the transmitter are visible Take note of the following Use only cleaning agents which do not corrode the housings nameplate and seals Use only cleaning methods corresponding to the housing protection rating 12 2 Rectify faults Reaction when malfunction occurs The operator of the system is responsible for taking suitable measures to rectify faul...
Page 85: ...Connect a multimeter in the suitable measuring range according to the wiring plan The following table describes possible errors in the current signal and helps to eliminate them Error Cause Rectification 4 20 mA signal not stable Fluctuating measured value Set damping Electrical connection faulty Check connection correct if necessary Voltage supply missing Check cables for breaks repair if necessa...
Page 86: ...ing worked on the measured value is temporarily invalid for example during simulation This status message is inactive by default Out of specification The measured value is unreliable because an transmitter specification was exceeded e g electronics temperature This status message is inactive by default Maintenance required Due to external influences the transmitter function is limited The measurem...
Page 87: ...eral software error Restart transmitter Byte 5 Byte 5 Bit 5 of Byte 0 5 F105 Determine measured value The transmitter is still in the start phase the measured value could not yet be determined Wait for the end of the switch on phase Duration up to 3 minutes depending on the measurement environment and parameter settings Byte 5 Byte 5 Bit 6 of Byte 0 5 F260 Error in the calibration Checksum error i...
Page 88: ... with transmitter data into the transmitter Bit 0 of Byte 14 24 M501 Error in the non active linearization table Hardware error EEPROM Send transmitter for repair Bit 1 of Byte 14 24 M504 Error at a device interface Bluetooth function disturbed Send transmitter for repair Bit 4 of Byte 14 24 M505 No echo available Transmitter does not detect an echo during operation Antenna dirty or defective Clea...
Page 89: ...mages in column Error description show the actual level as a dashed line and the output level as a solid line 1 Real level 2 Level displayed by the transmitter Note If the output level is constant the cause could also be the fault setting of the current output to Hold value If the level is too low the reason could be a line resistance that is too high Fault description Cause Rectification Min max ...
Page 90: ...se of interferences due to installations in the close range change polarisation direction Create a new auto false echo suppression Adapt max adjustment Measured value jumps towards 0 during filling The level echo cannot be distinguished from the false signal at a false signal position jumps to multiple echo In case of interferences due to installations in the close range Change polarisation direct...
Page 91: ... level echo Level echo too small Check measuring point Antenna should protrude out of the threaded mounting nozzle possible false echoes through flange nozzle Remove contamination on the antenna In case of interferences due to installations in the close range Change polarisation direction After eliminating the false signals the auto false echo suppression must be deleted Carry out a new auto false...
Page 92: ...on Chose a more suitable installation position Measured value jumps towards 0 during filling Transverse reflection from an extraction funnel amplitude of the transverse reflection larger than the level echo Direct transmitter to the opposite funnel wall avoid crossing with the filling stream Various echoes from an uneven medium surface e g a material cone Check parameter Material Type and adapt if...
Page 93: ...r contamination on the antenna Carry out auto false echo suppression or increase auto false echo suppression in the close range by editing Various echoes from an uneven medium surface e g an extraction funnel Check parameter Material Type and adapt if necessary Measured value fluctuates around 10 20 Reflections from the medium surface via the vessel wall deflection Optimize installation position a...
Page 94: ...dous substances Check the item after it has been cleaned Any devices replacement parts returned without a decontamination declaration will be cleaned at your expense before further processing 12 7 Technical support Technical Support If this documentation does not provide complete answers to any technical questions you may have contact technical support at http www siemens com automation support re...
Page 95: ...n Certificates You can find certificates in the Internet under http www siemens com processinstrumentation certificates or on an included DVD 12 8 How to proceed if a repair is necessary If it is necessary to repair the transmitter please contact Siemens You find the locations on www siemens com processautomation https www siemens com processautomation 86 SITRANS LR150 Operating Instructions 08 20...
Page 96: ...ual should be recycled They may not be disposed of in the municipal waste disposal services according to the Directive 2012 19 EC on waste electronic and electrical equipment WEEE Devices can be returned to the supplier within the EC or to a locally approved disposal service for eco friendly recycling Observe the specific regulations valid in your country Further information about devices containi...
Page 97: ...Service and maintenance 13 2 Disposal 88 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 98: ...ule in the device has been tested and approved according to the current edition of the applicable country specific norms or standards The confirmations as well as regulations for use can be found in the document Radio licenses supplied or on our homepage 14 2 EU conformity The device fulfils the legal requirements of the applicable EU directives By affixing the CE marking we confirm the conformity...
Page 99: ...Certificates and approvals 14 2 EU conformity 90 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 100: ...threaded connections only Materials non wetted parts Housing Plastic PBT Polyester Housing seals Silicone SI 850 R Cable gland PA Sealing cable gland NBR EPDM Blind plug cable gland PA Inspection window for the indication Polycarbonate Weight 0 7 kg 1 543 lbs Torques Max torque mounting boss 7 Nm 5 163 lbf ft Max torque for NPT cable glands and Conduit tubes 10 Nm 7 376 lbf ft Input variable Measu...
Page 101: ...Starting current 3 6 mA 10 mA for 5 ms after switching on Load 545 Ohm at 24 V DC Damping 63 of the input variable adjustable 0 999 s HART output values according to HART 7 0 a PV Primary Value Lin percent SV Secondary Value Distance TV Third Value Measurement reliability QV Fourth Value Electronics temperature Fulfilled HART specification 7 0 Further information on Manufacturer ID Device ID Devic...
Page 102: ...nt output due to digital analogue conversion 15 µA Additional deviation through electromagnetic interference According to NAMUR NE 21 80 µA According to EN 61326 1 None According to IACS E10 shipbuilding IEC 60945 250 µA Characteristics and performance data Measuring frequency W band 80 GHz technology Measuring cycle time a 250 ms Step response time b 3 s Beam angle c 8 a With operating voltage UB...
Page 103: ... x 1 5 cable diameter 5 9 mm Closing cap NPT Wire cross section spring loaded terminals Stranded wire 0 2 mm AWG 24 2 5 mm AWG 14 Bluetooth interface Bluetooth standard Bluetooth 5 0 downward compatible to Bluetooth 4 0 LE Frequency 2 402 2 480 GHz Max emitted power 2 2 dBm Max number of participants 1 Effective range typ a 25 m 82 ft a Depending on the local conditions Indication Measured value a...
Page 104: ...mpulse voltages 1 2 50 µs at 42 Ω 1000 V Additional overvoltage arrester Due to the floating structure of the electronics and comprehensive insulation measures generally not necessary Electrical protective measures Protection rating IP66 IP67 acc to IEC 60529Type 4X acc to UL 50 Altitude above sea level 5000 m 16404 ft Protection class III Pollution degree 4 15 2 Dimensions 1 Ventilation pressure ...
Page 105: ...are also used in this device A documentation of these components with the respective license type the associated license texts copyright notes and disclaimers can be found on our homepage 15 4 Trademark All the brands as well as trade and company names used are property of their lawful proprietor originator 96 SITRANS LR150 Operating Instructions 08 2020 A5E50352155 ...
Page 106: ...s www siemens com processautomation Industry Online Support service and support https support industry siemens com Industry Mall https mall industry siemens com Siemens AG Digital Industry Process Automation Postfach 48 48 90026 NÜRNBERG GERMANY ...