Setup with the integrated HMI
7.5.3 Quick setup volume
6
Level
Figure 7.7
Overview quick setup volume
Setting
Description
Reference point
Volume
VOL
Volume of the material in
volume unit (related to the level)
Lower calibration point
Material type
Used to optimize the device function depending on the type of material and vessel or
application:
Setting
Selection
Selection
Selection
STRGE
Vessel
PRCSS
Process vessel with agitation
WTWLL
Wet well
PLSTC
Outside of Plastic Tank
OPEN
Level of open liquid
LIQUID
DEMO MODE
Demonstration
SILO
Silo
BIN
Buffer, surge bin
MATERIAL TYPE
SOLID
OPEN
Heap, pile
Unit
UNITS:
Sets the measuring unit used (default setting in brackets):
• Meter "
m
"
(3 decimal places)
• Centimeter "
cm
"
(1 decimal place)
• Feet "
ft
"
(3 decimal places)
• Inches "
in
"
(2 decimal places)
Vessel shape
VESSEL SHAPE:
Sets the vessel shape and allows the device to calculate the volume instead of the
level:
• Linear vessel (LINR)
• Conical vessel bottom (CONIC)
• Container with flat sloping bottom (FLAT)
• Cylindrical vessel (CYLIN)
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155
39