Setup with the integrated HMI
7.7.8 Display
X-value 1 … X-value 32
Sets level index markers for which the output is known.
Y-value 1 … Y-value 32
Sets the output that corresponds to each input index marker entered.
7.7.8
Display
Start view
Sets the process value that appears first on the display after switching on.
Setting
Description
Level
LEVEL
Space
SPACE
Distance
DIST
VOL
Volume flow
VFLOW
Loop current
LOOPC
Percentage value
%
LOCL DISPLAY
Electronics temperature
STEMP
If the mode of operation is set accordingly
If the mode of operation is set accordingly
Note
If the parameter "
Operation
"
is set in the wizard, the value is automatically written
to
the parameter "
Start view
"
.
If the parameter "
Start view
"
or "
PV selector
"
is changed after the wizard has been
executed, the last change is valid.
The options "
Volume
"
, "
Volume flow
"
and "
Custom
"
are only visible in the
"
Measured
value view
"
if configured. If you select an option which is not configured
in the
parameter "
Start view
"
then the next visible process value appears in the
measured
value view.
54
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155