
Setup with the integrated HMI
7.4 Parameterization
7.4
Parameterization
Starting
From the measured value view, you can access the parameter view with the "
→
"
key,
and by pressing "
→
"
again you can access the first menu level.
Select
1.
Navigate to the desired parameter.
2.
Press "
→
"
to open the edit view. The current selection is highlighted.
3.
Scroll to a new selection with "
↓
"
and "
↑
"
.
4.
Press "
→
"
to confirm. The display returns to the parameter view and shows
the
new selection.
Change numeric value
1.
Navigate to the desired parameter.
2.
When selected, the current value is displayed.
3.
Press "
→
"
for configuration. The symbol "
EDIT
"
flashes.
4.
Use "
↑
"
and "
↓
"
to increase or decrease the value. Press and hold the button
to
increase the scroll speed.
5.
To cancel without saving your changes, press "
←
"
to return to the parameter
view.
6.
Press "
→
"
to confirm the new value. The display returns to the parameter view
(the "
EDIT
"
symbol is permanently displayed) and shows the new selection.
Check that the value is correct.
7.5
Quick setup
7.5.1
Wizards for quick setup
Overview
A wizard provides a simple step-by-step procedure to configure your device for a
basic application.
To configure the SITRANS LR150 for level, space, distance, volume or volume flow
applications, use the "
Quick Commissioning Wizard
"
via the display.
34
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155