Setup with the integrated HMI
7.3 Menu overview
Menu item
Parameter
Setting
Default
VFLOW UNITS = Level
Scaling: ScalingUnit
l/s, l/min, l/h, MI/d, m
3
/s, m
3
/min, m
3
/h, m
3
/
d, lb/s, lb/min, lb/h, gal/s, gal/min, gal/h,
gal/d, Mgal/d, ft
3
/s, ft
3
/min, ft
3
/h, ft
3
/d, bbl/
s, bbl/min, bbl/h, bbl/d, ImpGal/s, ImpGal/
min, Imp/Gal/h, ImpGal/d
l/s
SCALE FORMAT
Level Scaling: Decimal Places Display
0
UPPER SCALNG
Level Scaling: Max Scaled Value
100 l/s
AFES RANGE
Distance
00000
AFES
CONFIRM
Menu item
Parameter
Setting
Default
LEVEL
Level
SPACE
Space
DIST
Distance
VOL
Scaled value
VFLOW
Scaled value
CONF
Measurement reliability
DIST
SELECTION = Hart
Dynamic Variable
Channel: Device Variable
Code For SV
STEMP
Transmitter temperature
LINR
Linear
CYLIN
Horizontal cylindrical vessel
VENTU
Venturi-, trapezoidal weir,
rectangle weir
PALM
Flow Palmer-Bowlus flume
V-NOT
Flow VNotch-, triangle weir
CONIC
Conical Bottom
SELECT
OUTPUT
LINEARIZTYPE =
Linearization Curve Type
FLAT
Inclined Bottom
Linear
SENSOR
UNITS = Device Units:
Physical Value Unit
mm, m, in, ft
m
LOWER CAL PT
Level Adjustment Data
15 m
UPPER CAL PT
Level Adjustment Data
0 m
CALIBRATION
SENSR OFFSET
Offset Application Value
0 m
LOOP CUR MDE =
Display_Read Write Hart
Parameter. Loop Current
Mode
ON = Enabled (4 … 20 mA)
OFF = Disabled (4 mA fixed)
ON
DAMPING =
Level_Integration Time.
Responsetime
0 … 999 s
0 s
OUT CHARACT = Main
Current Output_
Configuration: Gradient
Type
4 … 20 mA = rising gradient, 20 … 4 mA =
falling gradient
4 … 20 mA
CURRENT OUT
SATURATE CUR
= Main Current
Output_Configuration:
Current Limits
3.8 … 20.5 mA, 4 … 20 mA
3.8 … 20.5 mA
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155
31