Diagnostics and troubleshooting
12.4 Status messages according to NE 107
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
no measured
value available
Clean the antenna system
F017
Adjustment span
too small
Adjustment not within
specification
Change adjustment according
to the limit values (difference
between min. and max.
≥ 10 mm)
Byte 5, Bit 1 of
Byte 0 … 5
F025
Error in the
linearization
table
Index markers are not
continuously rising, for
example illogical value pairs
Check linearization table
Delete table/Create new
Byte 5, Bit 2 of
Byte 0 … 5
F036
No operable
software
Checksum error if software
update failed or aborted
Repeat software update
Send transmitter for repair
Byte 5, Bit 3 of
Byte 0 … 5
F040
Error in the
electronics
Limit value exceeded in signal
processing
Hardware error
Restart transmitter
Send transmitter for repair
Byte 5, Byte 5,
Bit 4 of
Byte 0 … 5
F080
General software
error
General software error
Restart transmitter
Byte 5, Byte 5,
Bit 5 of
Byte 0 … 5
F105
Determine
measured value
The transmitter is still in the
start phase, the measured
value could not yet be
determined
Wait for the end of the switch-
on phase
Duration up to 3 minutes
depending on the
measurement environment
and parameter settings
Byte 5, Byte 5,
Bit 6 of
Byte 0 … 5
F260
Error in the
calibration
Checksum error in the
calibration values
Error in the EEPROM
Send transmitter for repair
Byte 4, Bit 0 of
Byte 0 … 5
F261
Error in the
transmitter
settings
Error during setup
Auto false echo suppression
faulty
Error when carrying out a
reset
Repeat setup
Carry out a reset
Byte 4, Bit 1 of
Byte 0 … 5
F265
Measurement
function
disturbed
Program sequence of the
measuring function disturbed
Device restarts automatically
Byte 4, Bit 3 of
Byte 0 … 5
Function check
Code
Text message
Cause
Rectification
DevSpec
State in CMD 48
C700
Simulation active
A simulation is active
Finish simulation
Wait for the automatic end
after 60 mins.
Simulation Active
in "
Standardized
Status 0
78
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155