Setup with the integrated HMI
7.7.5 Volume
Setting
Selection
Selection
Description
20 … 4 mA
Falling
Saturation limits
Sets the lower and upper saturation limits. The lower saturation limit is the value
below which the loop current cannot fall. The upper saturation limit is the value
above which the loop current cannot rise.
Setting
Selection
Selection
Description
3.8 … 20.5 mA
-
CURRENT OUT
SATURATE CUR
4 … 20 mA
-
Fault current
Sets the current value that is output in case of an error.
Setting
Selection
Selection
Description
≤ 3.6 mA
-
CURRENT OUT
FAULT CUR
≥ 21 mA
-
Safety function with echo loss
Defines the behavior of the safety function in case of echo loss and expiration of the
LOE timer. This defines which current value is output in case of echo loss.
Setting
Selection
Selection
Description
HOLD
Last valid measured value
CURRENT OUT
FAILSAFE LOE
FAULT
Value adjusted in the
parameter "
Fault current
"
Safety function LOE timer
LOE TIMER:
Sets the duration of how long an echo loss must be present before the device
triggers the set safety function.
7.7.5
Volume
50
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155