
Setup with the integrated HMI
7.7 Settings
3
Upper scaling point (0.6 m)
Figure 7.11
Application example volume flow
Quick
commissioning
parameter
Setting/value
Description
Operation
Volume flow
VFLOW
Material type
Liquid
LQD
Measuring
structure
Liquid
RWRC
Venturi flume
Lower calibration
point
1.6
Distance to the empty point
or bottom of the measuring
channel. Adjusts the material
level at 4 mA.
Upper calibration
point
1
Distance to maximum level.
Sets the "
Measurement end
"
.
Volume flow unit
VFLOW UNITS
Setting according to the
requirements of the end
user.
Unit
SCALE FORMAT
Unit which corresponds to
the level (head).
Measurement end
UPPER SCALNG
To be taken from the data
sheet of the manufacturer of
the measuring structure.
7.7
Settings
7.7.1
Selection HART variable
Secondary value
Sets a process value as secondary variable.
Setting
Selection
Selection
Description
LEVEL
Level
SPACE
Space
DIST
Distance
SELECT OUT
SELECT OUT
VOL
Volume
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155
47