Setup with the integrated HMI
7.5.3 Quick setup volume
• User-specific (USER)
Vessel dimension A
VESSEL DIM A:
Adjusts the height of the vessel bottom in case of a conical or flat sloping bottom.
Sets the height of the end piece for a horizontal tank with parabolic ends.
Lower calibration point
LOWER CAL PT:
Sets the distance from the transmitter reference point to the lower calibration point:
usually corresponds to the zero point of the process.
Upper calibration point
UPPER CAL PT:
Sets the distance from the transmitter reference point to the upper calibration point:
usually corresponds to the full level.
Volume unit
VOL UNITS:
Sets the measuring units for the volume.
• Litre (l)
• Hectolitre (hl)
• Cubic meters (m
3
)
• Cubic inches (in
3
)
• Gallons (gal)
• Cubic foot (ft
3
)
• Barrel (bbl)
Confirm
CONFIRM:
Accepts the settings as the last step in the wizard.
Setting Yes:
The wizard is closed and settings are applied.
40
SITRANS LR150
Operating Instructions, 08/2020,
A5E50352155