3 Mounting and Commissioning
470
7SD5 Manual
C53000-G1176-C169-1
3.1.3.3
Panel Surface Mounting
For mounting proceed as follows:
• Secure the device to the panel with four screws. For dimensions see the Technical
Data in Section 4.25.
• Connect the earth of the device to the protective earth of the panel. The cross-sec-
tional area of the earth wire must be equal to the cross-sectional area of any other
conductor connected to the device. The cross-section of the earth wire must be at
least 2.5 mm
2
.
• Connect solid, low-impedance operational earthing (cross-sectional area
≥
2.5
mm
2
) to the earthing surface on the side. Use at least one M4 screw for the device
earth.
• Make the connections according to the circuit diagram via the screwed-type termi-
nals. Fibre-optic cables and electrical communication modules are connected at the
inclined housings. The SIPROTEC
®
4 System Description has pertinent information
regarding wire size, lugs, bending radii, etc. You will find hints in the short descrip-
tion included in the device.
www
. ElectricalPartManuals