4.14 Time Overcurrent Protection
557
7SD5 Manual
C53000-G1176-C169-1
Further Definite Stage
Time factors
D
I
P
(phas-
es)
0.50 s to 15.00 s
or
∞
(ineffective)
Increments 0.01 s
D
3
I
0P
(earth)
0.50 s to 15.00 s
or
∞
(ineffective)
Increments 0.01 s
Additional time delays
T
I
P delayed
(phases)
0.00 s to 30.00 s
Increments 0.01 s
T
3
I
0P delayed
(earth)
0.00 s to 30.00 s
Increments 0.01 s
Characteristics
Tolerances currents
Pickup values at 1.05
≤
I
/
I
P
≤
1.15
or 1.05
≤
I
/3
I
0P
≤
1.15
Tolerances times
5 %
±
15 ms for 2
≤
I
/
I
P
≤
20 and D
I
P
/s
≥
1
or 2
≤
I
/3
I
0P
≤
20 and D
3
I
0P
/s
≥
1
Defined times
1 % of setting value or 10 ms
Pickup value
I
Ph
>>> (phases)
for
I
N
= 1 A 0.10 A to 25.00 A
or
∞
(ineffective)
Increments 0.01 A
for
I
N
= 5 A 0.50 A to 125.00 A
or
∞
(ineffective)
Pickup value 3
I
0
>>> (earth)
for
I
N
= 1 A 0.05 A to 25.00 A
or
∞
(ineffective)
Increments 0.01 A
for
I
N
= 5 A 0.25 A to 125.00 A
or
∞
(ineffective)
Delays
T
I
Ph
>>>
0.00 s to 30.00 s
or
∞
(ineffective)
Increments 0.01 s
T
3
I
0
>>>
0.00 s to 30.00 s
or
∞
(ineffective)
Increments 0.01 s
Dropout to pickup ratio
Approx. 0.95 for
I
/
I
N
≥
0.5
Pickup times (fast relays/high-speed relays)
approx. 30/25 ms
Dropout times
Approx. 30 ms
Tolerances currents
Currents
3 % of setting value or 1 % nominal current
Times
1 % of setting value or 10 ms
The set times are pure delay times.