2 Functions
134
7SD5 Manual
C53000-G1176-C169-1
1645
T5 DELAY
0.00 .. 30.00 sec;
∞
0.90 sec
T5 delay
1655
T1B-1phase
0.00 .. 30.00 sec;
∞
0.00 sec
T1B-1phase, delay for
single ph. faults
1656
T1B-multi-phase
0.00 .. 30.00 sec;
∞
0.00 sec
T1B-multi-ph, delay for
multi ph. faults
1657
1st AR -> Z1B
NO
YES
YES
Z1B enabled before 1st
AR (int. or ext.)
1901
PROGAM U/I
LE:Uphe/LL:Uphp
LE:Uphp/LL:Uphp
LE:Uphe/LL:Uphe
LE:Uphe/LL:I>>
LE:Uphe/LL:Uphp
Pickup program U/I
1902
DELAY FORW. PU
0.00 .. 30.00 sec;
∞
1.20 sec
Trip delay for Forward-
PICKUP
1903
DEL. NON-DIR PU
0.00 .. 30.00 sec;
∞
1.20 sec
Trip delay for non-direc-
tional PICKUP
1910
Iph>>
1A
0.25 .. 10.00 A
1.80 A
Iph>> Pickup (overcurrent)
5A
1.25 .. 50.00 A
9.00 A
1911
Iph>
1A
0.10 .. 4.00 A
0.20 A
Iph> Pickup (minimum cur-
rent)
5A
0.50 .. 20.00 A
1.00 A
1912
Uph-e (I>>)
20 .. 70 V
48 V
Undervoltage (ph-e) at
Iph>>
1913
Uph-e (I>)
20 .. 70 V
48 V
Undervoltage (ph-e) at
Iph>
1914
Uph-ph (I>>)
40 .. 130 V
80 V
Undervoltage (ph-ph) at
Iph>>
1915
Uph-ph (I>)
40 .. 130 V
80 V
Undervoltage (ph-ph) at
Iph>
1916
Iphi>
1A
0.10 .. 8.00 A
0.50 A
Iphi> Pickup (minimum
current at phi>)
5A
0.50 .. 40.00 A
2.50 A
1917
Uph-e (Iphi>)
20 .. 70 V
48 V
Undervoltage (ph-e) at
Iphi>
1918
Uph-ph (Iphi>)
40 .. 130 V
80 V
Undervoltage (ph-ph) at
Iphi>
1919A
EFFECT
ϕ
forward&reverse
Forward
forward&reverse
Effective direction of phi-
pickup
1920
ϕ
>
30 .. 60
°
50
°
PHI> pickup (lower set-
point)
1921
ϕ
<
90 .. 120
°
110
°
PHI< pickup (upper set-
point)
1930A
1ph FAULTS
PHASE-EARTH
PHASE-PHASEONLY
PHASE-EARTH
1ph-pickup loop selection
(PU w/o earth)
Addr.
Parameter
C
Setting Options
Default Setting
Comments