3.3 Commissioning
487
7SD5 Manual
C53000-G1176-C169-1
• Reset the interface parameters at the 7SD5 correctly:
– Address
4502
CONNEC. 1 OVER
= required setting, if you are testing the pro-
tection data interface 1,
– Address
4602
CONNEC. 2 OVER
= required setting, if are testing the protection
data interface 2.
• Disconnect the auxiliary supply voltage of the communication converter at both
poles. Note the above DANGER instruction!
• Reset the the communication converter to normal position (X32 in position 1-2) and
close the housing again.
• Reconnect the supply voltage of the communication converter.
Perform the above check at the other end with the device being connected there and
its corresponding communication converter.
Continue with the margin heading „Consistency of Topology and Parameterization“.
Consistency of To-
pology and Config-
uration
Having performed the above checks, the linking of a device pair, including their com-
munication converters, has been completely tested and connected to auxiliary supply
voltage. Now the devices communicate by themselves.
• Check now the Event Log or in the spontaneous annunciations of the device where
you are working:
– Message No. 3243
„PI1 with“
(protection data interface 1 linked with) fol-
lowed by the device index of the other device, if interface 1 is applying.
– Message No. 3244
„PI2 with“
(protection data interface 2 linked with) fol-
lowed by the device index of the other device, if interface 2 is applying.
– If the devices are at least connected once, the message No. 3458
„Chaintopology“
will appear.
– If no other devices are involved in the topology as an entity, the message No.
3464
„Topol complete“
will then be displayed, too.
– And if the device configuration is also consistent, i.e. the prerequisites for setting
the functional scope (Section 2.1.1), Power System Data 1 (2.1.2.1), Power
System Data 2 (2.1.4.1) topology and protection data interface parameters (Sec-
tion 2.2.2.1) have been considered, the fault message, i.e. No. 3229
„PI1 Data
fault“
or FNo. 3231
„PI2 Data fault“
for the interface just checked will
disappear. The communication and consistency test has now been completed.
– If the fault message of the interface being checked does not disappear, however,
the fault must be found and eliminated. Table 3-15 lists indications that indicate
such faults.
Table 3-15
Indications on inconsistencies
No.
Short Text
State
Meaning / Measures
3233 „DT
inconsistent“
ON
„Device table inconsistent“: the indexing of the devices is
inconsistent (missing numbers or one number used
twice, see Section 2.2.2.1)
3234 „DT unequal“
ON
„Device table unequal“: the ID-numbers of the devices
are unequal (see Section 2.2.2.1 )