4 Technical Data
564
7SD5 Manual
C53000-G1176-C169-1
4.18 Frequency Protection (optional)
Frequency Elements
Pickup Values
Times
Dropout Frequency
Operating Ranges
Tolerances
Quantity
4, depending on setting effective on f< or f>
f> or f< adjustable for each element
For f
N
= 50 Hz
45.50 Hz to 54.50 Hz
Increments 0.01 Hz
For f
N
= 60 Hz
55.50 Hz to 64.50 Hz
Increments 0.01 Hz
Pickup times f>, f<
Approx. 85 ms
Dropout times f>, f<
approx. 30 ms
Delay times T
0.00 s to 600.00 s
Increments 0.01 s
The set times are pure delay times.
Note on dropout times:
Dropout was enforced by current = 0 A and voltage = 0 V.
Enforcing the dropout by means of a frequency change below the dropout threshold extends the dropout times.
∆
f = | pickup value – dropout value |
Approx. 20 mHz
In voltage range
Approx. 6 V to 230 V (phase-earth)
In frequency range
25 Hz to 70 Hz
Frequencies f>, f< in specific range (f
N
±
10 %)
15 mHz in range U
LE
: 29 to 230 V
Time delays T(f<, f>)
1 % of setting value or 10 ms