2.16 Synchronism and Voltage Check (optional)
321
7SD5 Manual
C53000-G1176-C169-1
conditions“)! If you wish to permit manual closure or closing via control command only
under synchronous system conditions, set this address to
w/o T-CB close
.
The permissible difference between the voltages is set in address
3531
MC
maxVolt.Diff
. The setting is applied in Volts secondary. This value can be entered
as a primary value when parameterizing with a PC and DIGSI
®
. Depending on the VT
connection these are phase-to-earth voltages or phase-to-phase voltages.
The permissible frequency difference between the voltages is set at address
3532
MC
maxFreq.Diff
, the permissible phase angle difference at address
3533
MC
maxAngleDiff
.
The further release conditions for manual reclosing or reclosure via control command
are set under addresses
3535
to
3539
.
The following addresses mean:
3535
MC SYNCHR
The busbar (UBus) and the feeder (ULine) must both
be live (
Live Volt. Thr.
, address
3503
); the con-
ditions for synchronism are checked, i.e.
MC
maxVolt.Diff
(address
3531
),
MC maxFreq.Diff
(address
3532
) and
MC maxAngleDiff
(address
3533
). This parameter can only be altered with DIGSI
®
under
Additional Settings
.
3536
MC Usyn> Uline<
The busbar (UBus) must be live (
Live Volt. Thr.
,
address
3503
), the feeder (ULine) must be dead
(
Dead Volt. Thr.
, address
3502
);
3537
MC Usyn< Uline>
The busbar (UBus) must be dead (
Dead Volt.
Thr.
, address
3502
), the feeder (ULine) must be live
(
Live Volt. Thr.
, address
3503
);
3538
MC Usyn< Uline<
The busbar (UBus) and the feeder (ULine) must both
be dead (
Dead Volt. Thr.
, address
3502
);
3539
MC O/RIDE
Manual closing or closing via control command is re-
leased without any check.
The five possible release conditions are independent from each other and can be
combined.
Note
The closing functions of the device issue individual output indications for the corre-
sponding close command. Be sure that the output indications are assigned to the
correct output relays.
No. 2851
„AR CLOSE Cmd.“
for CLOSE via command of the automatic reclosure,
No. 562
„Man.Close Cmd“
for manual CLOSE via binary input,
No. 2961
„Sync.CloseCmd“
for CLOSE via synchronism check (not required if syn-
chronism check releases the other CLOSE commands),
No. 7329
„CB1-TEST close“
for CLOSE by circuit breaker test,
additionally CLOSE command via control, e.g.
„52 Close“
.
No. 510
„Relay CLOSE“
general CLOSE command. It comprises all CLOSE com-
mands described above.