2.22 Monitoring Functions
387
7SD5 Manual
C53000-G1176-C169-1
Table 2-16
Summary of malfunction responses of the device
Monitoring
Possible causes
Malfunction Re-
sponse
Indication (No.)
Device
AC/DC supply voltage
loss
External (aux. voltage) inter-
nal (converter)
Device out of operation
alarm, if possible
All LEDs dark
„Error 5V“ (144)
DOK
drops out
Measured value acqui-
sition
Internal (converter or refer-
ence voltage)
Protection out of opera-
tion, alarm
LED „ERROR“
„Error A/D-conv.“
(181)
DOK
drops out
Buffer battery
Internal (battery)
Indication
„Fail Battery“ (177)
As allocated
Hardware watchdog
Internal (processor failure)
Device not in operation LED „ERROR“
DOK
drops out
Software watchdog
Internal (program execution) Restart attempt
LED „ERROR“
DOK
drops out
Main memory
Internal (battery)
Restart attempt
Restart abort
Device not in operation
LED flashes
DOK
drops out
Program memory
Internal (EPROM)
Restart attempt
LED „ERROR“
DOK
drops out
Settings memory
internal (Flash-EPROM or
RAM)
Restart attempt
LED „ERROR“
DOK
drops out
Sampling frequency
Internal (clock generator)
Restart attempt
LED „ERROR“
DOK
drops out
1 A/5 A setting
Jumper wrong 1/5 A
Indications:
Protection out of opera-
tion
„Error1A/5Awrong“
(192) „Error A/D-
conv.“ (181)
LED „ERROR“
DOK
drops out
Calibration data
Internal (EEPROM or RAM) Indication:
Using default values
„Alarm adjustm.“
(193)
As allocated
Earth current transform-
er sensitive/insensitivity
I/O-BG does not comply with
the order number (MLFB) of
the device
Indications:
Protection out of opera-
tion
„Error neutralCT“
(194)„Error A/D-
conv.“ (181)
LED „ERROR“
DOK
drops out
Modules
Module does not comply
with order number (MLFB)
Indications:
Protection out of opera-
tion
„Error Board
BG1...7“ (183 ...
189)
and if applicable
„Error A/D-conv.“.
(181)
DOK
drops out
Current sum
Internal (measured value
acquisition)
Indication
Total blocking of the dif-
ferential protection
„Failure
Σ
i“ (289)
As allocated
Current balance
External (power system or
current transformer)
Indication
„Fail I balance“ (163) As allocated
Broken wire
External (power system or
current transformer)
Indication
Phase-selective block-
ing of the differential
protection
„Broken Iwire L1“
(290), „Broken Iwire
L2“ (291), „Broken
Iwire L3“ (292)
As allocated
Voltage sum
Internal (measured value
acquisition)
Indication
„Fail
Σ
U Ph-E“ (165) As allocated
Voltage symmetry
External (power system or
voltage transformer)
Indication
„Fail U balance“
(167)
As allocated
Voltage phase se-
quence
External (power system or
connection)
Indication
„Fail Ph. Seq.“ (171) As allocated