2.2 Protection Data Interfaces and Protection Data Topology
87
7SD5 Manual
C53000-G1176-C169-1
The device then issues one of the following error messages
•
„DT inconsistent“
(Device Table contains two or more identical device ident
numbers)
•
„DT unequal“
(Different settings of parameters
4701
to
4706
)
•
„Equal IDs“
(Protection system contains devices with identical settings of pa-
rameter
4710
)
If the indication
„Par. different“
is displayed OFF, the differential protection is
blocked as well. In this case the following parameters, which should have identical set-
tings in the devices, have in fact different settings.
• Address
230
Rated Frequency
• Address
143
TRANSFORMER
in the protected zone
• Address
1106
OPERATION POWER
primary
• Address
112
DIFF.PROTECTION
exists
• Address
149
charge I comp.
exists
2.2.3.2
Settings
2.2.3.3
Information List
Addr.
Parameter
Setting Options
Default Setting
Comments
4701
ID OF RELAY 1
1 .. 65534
1
Identification number of relay 1
4702
ID OF RELAY 2
1 .. 65534
2
Identification number of relay 2
4703
ID OF RELAY 3
1 .. 65534
3
Identification number of relay 3
4704
ID OF RELAY 4
1 .. 65534
4
Identification number of relay 4
4705
ID OF RELAY 5
1 .. 65534
5
Identification number of relay 5
4706
ID OF RELAY 6
1 .. 65534
6
Identification number of relay 6
4710
LOCAL RELAY
relay 1
relay 2
relay 3
relay 4
relay 5
relay 6
relay 1
Local relay is
No.
Information
Type of In-
formation
Comments
3451
>Logout
SP
> Logout input signal
3457
Ringtopology
OUT
System operates in a closed Ringtopology
3458
Chaintopology
OUT
System operates in a open Chaintopology
3464
Topol complete
OUT
Communication topology is complete
3475
Rel1Logout
IntSP
Relay 1 in Logout state
3476
Rel2Logout
IntSP
Relay 2 in Logout state
3477
Rel3Logout
IntSP
Relay 3 in Logout state
3478
Rel4Logout
IntSP
Relay 4 in Logout state
3479
Rel5Logout
IntSP
Relay 5 in Logout state
3480
Rel6Logout
IntSP
Relay 6 in Logout state
3484
Logout
IntSP
Local activation of Logout state