2.20 Circuit Breaker Failure Protection
371
7SD5 Manual
C53000-G1176-C169-1
Pole Discrepancy
Supervision
The pole discrepancy supervision can be switched
ON
or
OFF
independently at
address
3931
PoleDiscrepancy
. It is only useful if the breaker poles can be oper-
ated individually. It avoids that only one or two poles of the local breaker are open
during steady state. It has to be provided that either the auxiliary contacts of each pole
or the series connection of the NO auxiliary contacts and the series connection of the
NC auxiliary contacts are connected to the device's binary inputs. If these conditions
are not fulfilled, switch address
3931
OFF
.
The delay time
T-PoleDiscrep.
(address
3932
) determines how long a breaker
pole discrepancy condition of the feeder circuit breaker, i.e. only one or two poles
open, may be present before the pole discrepancy supervision issues a three-pole trip
command. This time must clearly be longer than the duration of a single-pole automat-
ic reclose cycle. The time should be less than the permissible duration of an unbal-
anced load condition which is caused by the unsymmetrical position of the circuit
breaker poles. Conventional values are 2 s to 5 s.
2.20.3 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
3901
FCT BreakerFail
ON
OFF
ON
Breaker Failure Protection
is
3902
I> BF
1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3903
1p-RETRIP (T1)
NO
YES
YES
1pole retrip with stage T1
(local trip)
3904
T1-1pole
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 1pole start
(local trip)
3905
T1-3pole
0.00 .. 30.00 sec;
∞
0.00 sec
T1, Delay after 3pole start
(local trip)
3906
T2
0.00 .. 30.00 sec;
∞
0.15 sec
T2, Delay of 2nd stage
(busbar trip)
3907
T3-BkrDefective
0.00 .. 30.00 sec;
∞
0.00 sec
T3, Delay for start with de-
fective bkr.
3908
Trip BkrDefect.
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
Trip output selection with
defective bkr
3909
Chk BRK CONTACT
NO
YES
YES
Check Breaker contacts
3921
End Flt. stage
ON
OFF
OFF
End fault stage is
3922
T-EndFault
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay of end fault
stage
3931
PoleDiscrepancy
ON
OFF
OFF
Pole Discrepancy supervi-
sion
3932
T-PoleDiscrep.
0.00 .. 30.00 sec;
∞
2.00 sec
Trip delay with pole dis-
crepancy