2 Functions
272
7SD5 Manual
C53000-G1176-C169-1
The following figure shows the logic diagram. The setting parameter addresses of the
IEC characteristics are shown by way of an example. In the setting information (Sec-
tion 2.14.3) the different setting addresses are elaborated upon.
Figure 2-118
Logic diagram of the
I
P
-stage (inverse time overcurrent protection), for example IEC characteristic
Additional Stage
I>>>
The additional definite time or instantaneous overcurrent stage
I
-STUB has an extra
enable input (Figure 2-119). It is therefore also suitable e.g. as an emergency stage.
The enable input
„>I-STUB ENABLE“
can be assigned to the output signal
„Emer.
mode“
(either via binary outputs and inputs or via the user-definable logic CFC func-
tions). The stage is then automatically active when the differential protection is not ef-
fective due to a data disturbance, and the distance protection due to a failure of the
measuring voltage.
www
. ElectricalPartManuals
. com