A.7 Settings
629
7SD5 Manual
C53000-G1176-C169-1
3140
Op. mode 3I0p
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3141
3I0p PICKUP
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
1A
0.05 .. 25.00 A
1.00 A
3I0p Pickup
5A
0.25 .. 125.00 A
5.00 A
3141
3I0p PICKUP
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
1A
0.003 .. 25.000 A
1.000 A
3I0p Pickup
5A
0.015 .. 125.000 A
5.000 A
3142
3I0p MinT-DELAY
Earth Fault O/C
0.00 .. 30.00 sec
1.20 sec
3I0p Minimum Time Delay
3143
3I0p Time Dial
Earth Fault O/C
0.05 .. 3.00 sec;
∞
0.50 sec
3I0p Time Dial
3144
3I0p Time Dial
Earth Fault O/C
0.50 .. 15.00 ;
∞
5.00
3I0p Time Dial
3145
3I0p Time Dial
Earth Fault O/C
0.05 .. 15.00 sec;
∞
1.35 sec
3I0p Time Dial
3146
3I0p MaxT-DELAY
Earth Fault O/C
0.00 .. 30.00 sec
5.80 sec
3I0p Maximum Time Delay
3147
Add.T-DELAY
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
0.00 .. 30.00 sec;
∞
1.20 sec
Additional Time Delay
3148
3I0p Telep/BI
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
3149
3I0p SOTF-Trip
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
YES
NO
Instantaneous trip after Switch-
OnToFault
3150
3I0p InrushBlk
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
Earth Fault O/C
NO
YES
NO
Inrush Blocking
3151
IEC Curve
Earth Fault O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
3152
ANSI Curve
Earth Fault O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
3153
LOG Curve
Earth Fault O/C
Log. inverse
Log. inverse
LOGARITHMIC Curve
3154
3I0p Startpoint
Earth Fault O/C
1.0 .. 4.0
1.1
Start point of inverse characteris-
tic
3155
k
Earth Fault O/C
0.00 .. 3.00 sec
0.50 sec
k-factor for Sr-characteristic
3156
S ref
Earth Fault O/C
1A
1 .. 100 VA
10 VA
S ref for Sr-characteristic
5A
5 .. 500 VA
50 VA
3160
POLARIZATION
Earth Fault O/C
U0 + IY or U2
U0 + IY
with IY only
with U2 and I2
zero seq. power
U0 + IY or U2
Polarization
3162A
Dir. ALPHA
Earth Fault O/C
0 .. 360
°
338
°
ALPHA, lower angle for forward
direction
3163A
Dir. BETA
Earth Fault O/C
0 .. 360
°
122
°
BETA, upper angle for forward di-
rection
3164
3U0>
Earth Fault O/C
0.5 .. 10.0 V
0.5 V
Min. zero seq.voltage 3U0 for po-
larizing
3165
IY>
Earth Fault O/C
1A
0.05 .. 1.00 A
0.05 A
Min. earth current IY for polariz-
ing
5A
0.25 .. 5.00 A
0.25 A
3166
3U2>
Earth Fault O/C
0.5 .. 10.0 V
0.5 V
Min. neg. seq. polarizing voltage
3U2
3167
3I2>
Earth Fault O/C
1A
0.05 .. 1.00 A
0.05 A
Min. neg. seq. polarizing current
3I2
5A
0.25 .. 5.00 A
0.25 A
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments