2.24 Ancillary Functions
415
7SD5 Manual
C53000-G1176-C169-1
Figure 2-184
Local measured values — example for voltages and currents
2.24.1.2 Setting Notes
The parameters of the „IBS-Tool“ can be set separately for the front operator interface
and the service interface. The relevant addresses are those which relate to the inter-
face that is used for communication with the PC and the „IBS-Tool“.
Addresses
4401
to
4406
are to configure the front interface. The valid 12-digit IP
address has the format ***.***.***.***. A three-digit block of the IP address is inserted
into each of the addresses
4401
IP-A (A.x.x.x)
,
4402
IP-B (x.B.x.x)
,
4403
IP-C (x.x.C.x)
and
4404
IP-D (x.x.x.D)
.
The address
4405
NUM LOCK
determines if the devices of a differential protection
system should be operated with the IBS-Tool from the PC. When setting
YES
, the
devices cannot be operated by the front panel emulation of the PC. This is the normal
state during operation. Once this address is set to NO during commissioning, all
device parameters can be changed to correct, for example, false or inconsistent set-
tings.
In address
4406
LCP/NCP
set if your PC interface supports LCP (Link Control Proto-
col) and NCP (Network Control Protocol). In the case of a point-to-point connection,
the setting must be
YES
(default setting) to allow a data communications link. When
using a star coupler, only one device (master device) requires the setting
YES
, the
other devices require
NO
.
Addresses
4411
IP-A (A.x.x.x)
,
4412
IP-B (x.B.x.x)
,
4413
IP-C
(x.x.C.x)
,
4414
IP-D (x.x.x.D)
,
4415
NUM LOCK
and
4416
LCP/NCP
. are to
configure the rear interface.