A Appendix
622
7SD5 Manual
C53000-G1176-C169-1
1504
3U0> Threshold
Dis. General
1 .. 100 V;
∞
5 V
3U0 threshold zero seq. voltage
pickup
1505
3U0> COMP/ISOL.
Dis. General
10 .. 200 V
40 V
3U0> pickup (comp/ isol. star-
point)
1507A
3I0>/ Iphmax
Dis. General
0.05 .. 0.30
0.10
3I0>-pickup-stabilisation (3I0>
/Iphmax)
1508
SER-COMP.
Dis. General
NO
YES
NO
Series compensated line
1509A
E/F recognition
Dis. General
3I0> OR 3U0>
3I0> AND 3U0>
3I0> OR 3U0>
criterion for earth fault recogni-
tion
1510
Start Timers
Dis. General
on Dis. Pickup
on Zone Pickup
on Dis. Pickup
Condition for zone timer start
1515
Paral.Line Comp
Dis. General
NO
YES
YES
Mutual coupling parall.line com-
pensation
1520
PHASE PREF.2phe
Dis. General
L3 (L1) ACYCLIC
L1 (L3) ACYCLIC
L2 (L1) ACYCLIC
L1 (L2) ACYCLIC
L3 (L2) ACYCLIC
L2 (L3) ACYCLIC
L3 (L1) CYCLIC
L1 (L3) CYCLIC
All loops
L3 (L1) ACYCLIC
Phase preference for 2ph-e faults
1521A
2Ph-E faults
Dis. General
Block leading Ø
Block lagging Ø
All loops
Ø-Ø loops only
Ø-E loops only
Block leading Ø
Loop selection with 2Ph-E faults
1532
SOTF zone
Dis. General
PICKUP
Zone Z1B
Inactive
Z1B undirect.
Inactive
Instantaneous trip after Switch-
OnToFault
1533
Z1 blkd by diff
Dis. General
YES
NO
YES
Zone Z1 blocked by diff. active
1540
Distance Angle
P.System Data 2
Dis. General
30 .. 90
°
85
°
Angle of inclination, distance
charact.
1541
R load (Ø-E)
Dis. General
1A
0.100 .. 600.000
Ω
;
∞
∞ Ω
R load, minimum Load Imped-
ance (ph-e)
5A
0.020 .. 120.000
Ω
;
∞
∞ Ω
1542
ϕ
load (Ø-E)
Dis. General
20 .. 60
°
45
°
PHI load, maximum Load Angle
(ph-e)
1543
R load (Ø-Ø)
Dis. General
1A
0.100 .. 600.000
Ω
;
∞
∞ Ω
R load, minimum Load Imped-
ance (ph-ph)
5A
0.020 .. 120.000
Ω
;
∞
∞ Ω
1544
ϕ
load (Ø-Ø)
Dis. General
20 .. 60
°
45
°
PHI load, maximum Load Angle
(ph-ph)
1601
Op. mode Z1
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z1
1602
R(Z1) Ø-Ø
Dis. Quadril.
1A
0.050 .. 600.000
Ω
1.250
Ω
R(Z1), Resistance for ph-ph-
faults
5A
0.010 .. 120.000
Ω
0.250
Ω
1603
X(Z1)
Dis. Quadril.
1A
0.050 .. 600.000
Ω
2.500
Ω
X(Z1), Reactance
5A
0.010 .. 120.000
Ω
0.500
Ω
1604
RE(Z1) Ø-E
Dis. Quadril.
1A
0.050 .. 600.000
Ω
2.500
Ω
RE(Z1), Resistance for ph-e
faults
5A
0.010 .. 120.000
Ω
0.500
Ω
1605
T1-1phase
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.00 sec
T1-1phase, delay for single
phase faults
1606
T1-multi-phase
Dis. General
Dis. Quadril.
Dis. MHO
0.00 .. 30.00 sec;
∞
0.00 sec
T1multi-ph, delay for multi phase
faults
1607
Zone Reduction
Dis. Quadril.
0 .. 45
°
0
°
Zone Reduction Angle (load
compensation)
1611
Op. mode Z2
Dis. Quadril.
Forward
Reverse
Non-Directional
Inactive
Forward
Operating mode Z2
Addr.
Parameter
Function
C
Setting Options
Default Setting
Comments