2.14 Backup Time Overcurrent Protection
281
7SD5 Manual
C53000-G1176-C169-1
Instantaneous tripping when the line is switched onto a fault is also possible with the
I
-STUB stage. Set parameter
I-STUB SOTF
(address
2635
) to
YES
, if instantaneous
tripping is desired.
2.14.4 Settings
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2601
Operating Mode
ON
Only Emer. prot
OFF
ON
Operating mode
2610
Iph>>
1A
0.10 .. 25.00 A;
∞
2.00 A
Iph>> Pickup
5A
0.50 .. 125.00 A;
∞
10.00 A
2611
T Iph>>
0.00 .. 30.00 sec;
∞
0.30 sec
T Iph>> Time delay
2612
3I0>> PICKUP
1A
0.05 .. 25.00 A;
∞
0.50 A
3I0>> Pickup
5A
0.25 .. 125.00 A;
∞
2.50 A
2613
T 3I0>>
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0>> Time delay
2614
I>> Telep/BI
NO
YES
YES
Instantaneous trip via Tele-
prot./BI
2615
I>> SOTF
NO
YES
NO
Instantaneous trip after
SwitchOnToFault
2620
Iph>
1A
0.10 .. 25.00 A;
∞
1.50 A
Iph> Pickup
5A
0.50 .. 125.00 A;
∞
7.50 A
2621
T Iph>
0.00 .. 30.00 sec;
∞
0.50 sec
T Iph> Time delay
2622
3I0>
1A
0.05 .. 25.00 A;
∞
0.20 A
3I0> Pickup
5A
0.25 .. 125.00 A;
∞
1.00 A
2623
T 3I0>
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0> Time delay
2624
I> Telep/BI
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
2625
I> SOTF
NO
YES
NO
Instantaneous trip after
SwitchOnToFault
2630
Iph> STUB
1A
0.10 .. 25.00 A;
∞
1.50 A
Iph> STUB Pickup
5A
0.50 .. 125.00 A;
∞
7.50 A
2631
T Iph STUB
0.00 .. 30.00 sec;
∞
0.30 sec
T Iph STUB Time delay
2632
3I0> STUB
1A
0.05 .. 25.00 A;
∞
0.20 A
3I0> STUB Pickup
5A
0.25 .. 125.00 A;
∞
1.00 A
2633
T 3I0 STUB
0.00 .. 30.00 sec;
∞
2.00 sec
T 3I0 STUB Time delay
2634
I-STUB Telep/BI
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
2635
I-STUB SOTF
NO
YES
NO
Instantaneous trip after
SwitchOnToFault