● Long-term storage
● Transport
● Operation
Class 1B1 according to EN 60721-3-1, in product packaging
1)
Class 2B1 according to EN 60721-3-2, in transport packaging
2)
Class 3B1 according to EN 60721-3-3
Mechanical environmental conditions
● Long-term storage
● Transport
● Operation (central components)
Vibration test in operation
Shock test in operation
● Operation (distributed components)
Class 1M2 according to EN 60721-3-1, in product packaging
1)
Class 2M3 according to EN 60721-3-2, in transport packaging
2)
Class 3M1 according to EN 60721-3-3
According to IEC 60068-2-6 test Fc (sinusoidal)
● 10 ... 57 Hz: 0.075 mm deflection amplitude
● 57 ... 150 Hz: 1 g acceleration amplitude
● 10 frequency cycles per axis
According to IEC 60068-2-27 test Ea (half-sine)
● 5 g peak acceleration
● 30 ms duration
● 3 shocks in all three axes in both directions
Class 3M3 according to EN 60721-3-3
For details, see the relevant technical data (S120M, DQE)
Climatic environmental conditions
● Long-term storage
● Transport
● Operation for SINAMICS S120 and AM600 central
components
● Operation for SINAMICS S120M distributed
components
Class 1K4 according to EN 60721-3-1, in product packaging
1)
Temperature: -25 … +55 °C
Class 2K4 according to EN 60721-3-2, in transport packaging
2)
Temperature: -40 … +70 °C
Class 3K3 according to EN 60721-3-3 with increased ruggedness
with respect to relative humidity
Temperature: 0 ... +40 °C without derating
> 40 ... +55 °C with reduction of the output current by 2.67% per °C
Relative humidity: 5 … 95% no condensation (better than Class
3K3)
Oil mist, salt mist, ice formation, condensation, dripping water,
spraying water, splashing water and water jets are not permitted
Class 3K3 according to EN 60721-3-3 with increased ruggedness
with respect to relative humidity
Temperature: -15 ... +40 °C without derating
>40... +55 °C with reduction of the output current by 2.67% per °C
Relative humidity: 5 … 95% no condensation (better than Class
3K3)
Oil mist, salt mist, ice formation, condensation, dripping water,
spraying water, splashing water and water jets are not permitted
System overview
3.5 System Data
52
Manual, 06/2019, 6SL3097-5AW00-0BP1
Summary of Contents for Sinamics S120M
Page 2: ......
Page 20: ...Introduction 1 8 General Data Protection Regulation 18 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 56: ...System overview 3 5 System Data 54 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 110: ...S120M 5 11 Motor holding brake 108 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 118: ...DRIVE CLiQ Extension 6 6 Technical data 116 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 126: ...Hybrid Cabinet Bushing 7 6 Technical data 124 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 182: ...Appendix A 2 Documentation overview 180 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 185: ......