An alarm is output if a line with distributed drives is not terminated using a line termination
connector.
Line termination connector
S120M with line termination connector
After connecting it, tighten the termination connector so that it cannot be released using the tool
provided.
● Tool: Allen key
● Tightening torque: 3.0 Nm (26.6 lbf in)
The line termination connector is included in the package enclosed with the AM600.
Missing line termination connectors can be reordered as spare parts with the following Article
No.: 6SL3566-2DC00-0AA0.
Changing over the outlet direction of the line termination connector
If you require a line termination connector in the opposite outlet direction, then you can change
this yourself by rotating the plug insert through 180°.
WARNING
Hazardous voltage when changing over the plug inserts of prefabricated hybrid cables
For prefabricated hybrid cables, it is not permissible to change over the plug inserts
(see Hybrid cable (Page 135)). Hazardous touch voltages could occur, which could lead to
severe injury or death.
● Only change over plug inserts for line termination connectors.
Control cabinet design
8.6 Layout of the components
152
Manual, 06/2019, 6SL3097-5AW00-0BP1
Summary of Contents for Sinamics S120M
Page 2: ......
Page 20: ...Introduction 1 8 General Data Protection Regulation 18 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 56: ...System overview 3 5 System Data 54 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 110: ...S120M 5 11 Motor holding brake 108 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 118: ...DRIVE CLiQ Extension 6 6 Technical data 116 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 126: ...Hybrid Cabinet Bushing 7 6 Technical data 124 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 182: ...Appendix A 2 Documentation overview 180 Manual 06 2019 6SL3097 5AW00 0BP1 ...
Page 185: ......