Figure 8-16
Type 1 Pre-charge Component Connections
Sequence of Operation
1. To start pre-charge,
DriveReadyToPrecharge_I
must be
true.
PrechargeStartEnable_O
is set true to start the sequence.
2. M2 is closed to begin resonance by connecting a capacitor in series with the
secondary,
PrechargeM2Close_I
is set equal to true.
3. When the input primary voltage reaches the max phase voltage set by the parameter
"Precharge voltage level" (2634), a damping resistor is connected through
M3.
PrechargeM3Close_I
is set equal to true.
4. The M3 acknowledge comes back,
PrechargeM3CloseAck_O
is set equal to true. M2
contactor is commanded to open,
PrechargeM2Close_I
is set equal to false.
5. The M2 acknowledge comes back,
PrechargeM2CloseAck_O
is set equal to true. M1
contactor is commanded to close,
PrechargeM1Close_I
is set equal to true.
Advanced Operating Functions
8.18 Pre-charge using SOP
Control Manual
Operating Manual, A5E50491925A
291
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......