Note
Tripped Pre-charge Circuit Breaker Occurrences
The pre-charge circuit breaker shall be tripped if any of the following occurs:
• Over-voltage (>115%) occurs during pre-charge
• Under-Voltage Trip (PCVMRStatus_O)
• Input Protection Fault
• LFR Trip
• PB4/E-Stop
• M2 Contactor Open Status Failure
• Trip_CB2 (TripPrechargeCB2_O) is asserted
The SOP input control flags below are available for particular cell types using the pre-charge
function by selecting Type 4 pre-charge. No dedicated inputs are used.
Table 5-3
Type 4 SOP Input Control Flags
Flag
Function
Description
StartCellPrecharge_O
PrechargeRequest
Request to start pre-charge
PrechargeM2CloseAck_O
M2CloseACK
Feedback of M2 contact
PrechargeM1CloseAck_O
M1CloseACK
Feedback of M1 contact
TripPrechargeCB2_O (SOP)
TripPrechargeCB2
Request trip of pre-charge CB
PCVMRStatus_O
PCVMRStatus
Precharge voltage (CB UV trip) status - '1' = voltage okay
CB2Status_O
CB2Status
Precharge CB status - '1' = CB is closed
There are 16 digital outputs on the first user I/O board:
• DO-0 to DO-15
There is one digital output on the system interface board:
• SIB M1 DOUT
Table 5-4
Type 4 Dedicated and SOP Outputs
Dedicated Output*
Terminal
SOP Feedback
Function
Description
DO-14
J4-7, 8, 9
CIMVType4
CIMV
Command to close M1
PrechargeM2Close_I
Assigned out‐
put
SOP determined
M2Close
Command to close M2
OpenPrechargeCB_I
Assigned out‐
put
SOP determined
BreakerTrip
Command to open (trip) pre-charge supply
breaker
M1 DOUT
SIB 51, 53, 55 M1Permit‐
Closed_I
M1Close
Permissive
(TIMV)
If this signal is de-energized, the drive’s medi‐
um voltage will trip immediately.
If the signal is not energized, it will be an in‐
hibit.
* Dedicated Output: Refer to specific drive wiring diagram for dedicated output designations
Hardware User Interface Description
5.3 User Accessible Interfaces
Control Manual
78
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......