Fault display
Type
Enable
Potential causes and corrective actions
Modulator watchdog flt
F
Fixed
Cause
Modulator detected that the CPU stopped communicating with it.
Action
1. Reset drive control power.
2. Check for proper grounding practices.
3. Replace DCR.
Loss of drive enable
F
SOP
Cause
Modulator detected loss of drive enable.
Action
1. Reset drive control power.
2. Check for proper grounding practices.
Troubleshooting Faults and Alarms
11.7 Drive Faults and Alarms Modulator Related
Control Manual
458
Operating Manual, A5E50491925A