8.8
External Flux Reference
8.8.1
External Flux Reference Introduction
For certain synchronous motor types, the flux must be reduced for startup. This is mostly a
thermal problem with large inertial loads and virtually no cooling when the rotor is stationary.
This feature is enabled via a SOP flag that, when enabled, allows the flux demand to come
through a network register instead of using the internally computed value.
This feature can also be used to import a flux profile from an external device, i.e. PLC or PC, and
transfer to the motor via the network register.
8.8.2
External Flux Reference Parameters
Parameters for External Flux Reference
Location: Drive → Drive Protect → Input Protect
Parameters associated with external flux reference are detailed in the following table.
Parameter
ID
Units
Default
Min
Max
Description
Global Data to
Drive
9200
Sub-menu
Menu for Global registers for data sent to drive from
the network.
Data to Drive 01
-Drive 32
2201 to
2231
None
<picklist>
Global register that contains data sent from the net‐
work to drive. One of these registers must be set to
"Flux Demand" from the pick list to use the register
value.
Advanced Operating Functions
8.8 External Flux Reference
Control Manual
242
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......