Fault handling
To reset a fault manually, use the [FAULT RESET] key on the keypad. Return the drive to the run
condition by performing manual start or by forcing the
RunRequest_I
equal to "true".
Certain faults can be reset automatically if enabled by the auto fault reset enable (7120). Refer
to Table Auto resettable faults, for a list of auto resettable faults. These are fixed and not
adjustable. If reset is successful, the drive will return to the run state automatically only if the
RunRequest_I
is maintained at the value "true". The [FAULT RESET] key of the keypad is also
used to acknowledge alarms.
Table 7-4
Auto resettable faults
Over Speed Fault
Keypad Communication
Encoder Loss
Under Load Fault
Network 1 Communication
Loss of Signal 1 to 24
Output Ground Fault
Network 2 Communication
Int AI1 to AI12 Loss of Signal
IOC
Motor Over Volt Fault
Loss Of Drive Enable
Menu Initialization
Back EMF Timeout
Motor Pull-out Fault
Medium voltage low Flt
Failed To Magnetize
SMDC PLL Start-up Fault
Line Over Voltage Fault
Loss Of Field Current
SM Pole Slip
Operating the Control
7.15 Faults and Alarms
Control Manual
232
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......