Parameter
ID
Unit
Default
Min
Max
Description
Sampling Delay
Comp
3570
%
0.0
0.0
150.0
Compensate the flux vector angle for sampling
delay on high speed motor operation.
Carrier frequency
3580
Hz
600.0
100.0
1550.0
Enter the IGBT switching frequency. The control
adjusts the entered value according to available
resolution from the modulator registers, e.g., if
you enter 400.0, the actual frequency may be
398.6:
f
C
= Power cell carrier frequency
f
O
= Drive rated output frequency
For f
O
< 167 Hz, f
C
= 600 Hz is typically adequate.
A smaller value of f
C
can be chosen provided
300 Hz < f
C
> (3.6 x f
O
) Hz.
For f
O
= 167 to 330 Hz, 1550 Hz > f
C
> (3.6 x f
O
) Hz.
High switching frequencies may result in some
derating due to increased switching losses. Con‐
sult Siemens customer service for derating values.
Table 6-50
Input Processing Menu (3000) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
PLL prop gain
3010
70.0
0.0
200.0
Proportional gain of input phase-locked loop
(PLL).
PLL integral gain
3020
3840.0
0.0
12000.0
Integral gain of input PLL.
Input current scaler 3030
1.0
0.0
2.0
Set the scaling for input current feedback. Default
value is normally adequate.
CT secondary turns 3035
200
50
3000
Secondary side turns for input current CT, with
primary turns equal to 5.
Input voltage scaler 3040
1.0
0.0
2.0
Set the scaling for input line voltage feedback.
Default value is normally adequate.
PT secondary turns 3011
1
1
3000
Secondary turns input voltage PT.
VAR control
3041
Submenu
Access the cell input control parameters.
Input Attenuator
Sum
3045
kOhm
3000
1
32767
Set scaling for input nominal value. This is the
sum of the two input resistors per phase.
CAUTION
PLL gains and scaling parameter values
Changing PLL gains from the default values or setting scaling parameter values incorrectly can
cause unintended results that affect performance and disable drive protections.
Scaling parameter values must match actual hardware ratings.
Never change scaling parameter values from actual hardware ratings.
Parameter Assignment/Addressing
6.8 Options for Stability Menu (3) - first half
Control Manual
126
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......