• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed to be selected if the analog source is one of
the internal I/O inputs.)
Define the minimum and maximum values for scaling, and the loss of signal (LOS) threshold and
action.
Table 6-63
Analog Input #1 Menu (4100) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Source
4105
Off
Set the input source for analog input 1:
• Off
• Ext 1 to 24
• Int 1 to 12
See Table Pick list for Analog Input Sources.
Type
4110
4–20 mA
Set the operational mode for analog input 1:
• 0 to 20 mA
• 4 to 20 mA
• 0 to 10 V
• -10 V to +10 V (Note: This option is not allowed
to be selected if the analog source is one of the
internal I/O inputs.)
Min input
4120
%
0.0
-300.0 300.0
Minimum analog input.
Max input
4130
%
100.0
-300.0 300.0
Maximum analog input.
Loss point threshold 4140
%
15.0
0.0
100.0
Threshold where loss of signal action is activated.
Enter as a percentage of upper range for any type.
Loss of signal action 4150
Preset
Select loss of signal action:
• Preset
• Maintain
• Stop
Loss of signal set‐
point
4160
%
20.0
-200.0 200.0
Loss of signal preset speed.
Parameter Assignment/Addressing
6.11 Options for Auto Menu (4)
Control Manual
Operating Manual, A5E50491925A
139
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......