DO-xx*
Terminal
SOP Feedback
Function
Description
DO-13
J4-4, 5, 6
InternalDigitalOutput13
BreakerTrip
Command to open (trip) pre-
charge supply breaker
M1 DOUT
SIB 51, 53, 55 M1PermitClosed_I
M1Close Permissive
(TIMV)
If this signal is de-energized, the
drive’s medium voltage will trip
immediately.
If the signal is not energized, it
will be an inhibit.
* DO-xx: Refer to specific drive wiring diagram for DO-xx designations
5.3.12
Dedicated I/O for Input Protection (IP)
The following are dedicated I/O for input protection usage. Any cell type may use these
dedicated I/O if parameter Dedicated Input Protect (7108) is set "ON". If set to "OFF" this
dedicated I/O will not function unless air-cooled 6SR4_0 cells or water-cooled 6SR32x cells are
used. These cells must use dedicated inputs and outputs for IP faults, which are on by default.
Turning parameter Dedicated Input Protect (7108) off will be overridden by the software code
and still be active (on).
Table 5-7
Dedicated Inputs
DI-xx*
Terminal
SOP Feedback
Function
Description
DI-3E
J9-4
InternalDigitalInput3e_I
LFRInputProtectACK
Latch Fault Relay (LFR) status
* DI-xx: Refer to specific drive wiring diagram for DI-xx designations
Table 5-8
Dedicated Outputs
DO-xx*
Terminal
SOP Feedback
Function
Description
DO-15
J4-10, 11, 12 InternalDigitalOutput3e_I
LFRInputProtect
Command to set LFR (1 sec
pulse)
M1 DOUT
SIB 51, 53, 55 M1PermitClosed_I
M1Close Permissive
(TIMV)
If this signal is de-energized, the
drive’s medium voltage will trip
immediately.
If the signal is not energized, it
will be an inhibit.
* DO-xx: Refer to specific drive wiring diagram for DO-xx designations
Cell Types when Dedicated I/O is not used
For all cell types that do not have dedicated I/O assignments or if the user I/O board is not used,
(i.e. when using WAGO I/O), internal digital I/O must be mapped to SOP flags associated with the
function. The flags are entirely controlled via the SOP.
Hardware User Interface Description
5.3 User Accessible Interfaces
Control Manual
80
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...