Set active config file
Use this pick list to set the displayed file to be the active configuration
file.
This function overrides what is set in the SOP. Any change in the SOP
is checked against the file set in this function. Once a change in the
SOP is detected, that file will then be the active file. The keypad menu
setting is now ignored. This ensures no unintentional toggling of the
configuration files.
To switch back to the keypad file set it by this menu. If no change in the
SOP occurs, the keypad set configuration file will remain in memory.
Setup SOP config flags Use this submenu for SOP flag configuration.
Create new config file
Use this function to save slave parameters to a file name you specify.
Use the drive keypad to enter the file name. To get to the alphanu‐
meric characters, use the left or right arrow keys to position the cur‐
sor. Use the up or down arrow keys to scroll to the desired letter or
number.
Set
SOPConfigFileX_O
Use this function to map the name of the flag in the SOP
file,
SOPConfigFileX_O
(X = 1 to 8) to a name of a slave configu‐
ration file.
Once the SOP is running, and this flag is set to ‘true’, the configuration
file will be switched into memory. This is a method of switching
among multiple motors using one drive.
Select the file names from a pick list or create new files as described.
Table 6-102 Slave Setup and Configuration Parameters
Parameter
ID
Units
Default
Min
Max
Description
Multiple config files
9185
Off
Enable multiple configuration file opera‐
tion.
Show active config file
9195
Display the current active configuration file
on the flash disk.
Set active config file
9196
defaults.sfg
Set the displayed file to be the active con‐
figuration file on the flash disk.
Setup SOP config flags
9186
Submenu
Access menu for SOP flag configuration.
Create new config file
9197
Create a new configuration file using the
numeric keypad.
Set SOPConfigFile1_O
9187
defaults.sfg
Set the name of configuration file 1 to be
used with corresponding SOP flag 1.
Set SOPConfigFile2_O
9188
defaults.sfg
Set the name of configuration file 2 to be
used with corresponding SOP flag 2.
Set SOPConfigFile3_O
9189
defaults.sfg
Set the name of configuration file 3 to be
used with corresponding SOP flag 3.
Set SOPConfigFile4_O
9190
defaults.sfg
Set the name of configuration file 4 to be
used with corresponding SOP flag 4.
Set SOPConfigFile5_O
9191
defaults.sfg
Set the name of configuration file 5 to be
used with corresponding SOP flag 5.
Set SOPConfigFile6_O
9192
defaults.sfg
Set the name of configuration file 6 to be
used with corresponding SOP flag 6.
Parameter Assignment/Addressing
6.19 Options for Multiple Configuration Files
Control Manual
172
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......