6.9
Options for Stability Menu (3) - second half
Table 6-56
Speed Loop Menu (3200) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Speed reg prop gain 3210
0.02
0.0
1.0
Speed PI regulator proportional gain term.*
Speed reg integral
gain
3220
0.046
0.0
1200.0
Speed PI regulator integral gain term.*
Speed reg Kf gain
3230
0.6
0.1
1.0
Allows a smooth variation of the speed regulator
from a simple PI (Kf = 1.0) to a double speed loop
(Kf = 0.5).
Speed filter time
const
3240
0.0488
0.0
10.0
Time constant of the low pass filter used on the
speed error.*
Droop in % @ FL cur‐
rent
3245
%
0.0
0.0
10.0
Desired speed droop in percent of rated speed at
full load current. Enter 0 to disable.
* Values are automatically calculated after Stage 2 auto-tuning.
Refer to Section Auto-tuning of Chapter Operating the Control for warnings associated with
this function.
Table 6-57
Current Loop Menu (3250) Parameters
Parameter
ID
Unit
Default
Min
Max
Description
Current reg prop
gain
3260
0.5
0.0
5.0
Current PI regulator proportional gain term.*
Current reg integ
gain
3270
25.0
0.0
6000.0
Current PI regulator integral gain term.*
Current reg prop
gain2
3271
0.5
0.0
5.0
Current PI regulator second proportional gain
term.
Current reg integ
gain2
3272
25.0
0.0
6000.0
Current PI regulator second integral gain term.
Prop gain during
brake
3280
0.16
0.0
5.0
Current PI regulator proportional during dual fre‐
quency braking.*
Integ gain during
brake
3290
9.6
0.0
6000.0
Current PI regulator integral gain term during dual
frequency braking.*
* Values are automatically updated after Stage 1 auto-tuning.
Secondary current loop gains that can switch quickly without interrupting the running
process based on the SOP flag EnableSecondCurrentGains_O.
When EnableSecondGains_O = False --> gain set 3260 and 3270 is used (normal).
When EnableSecondGains_O = True --> gain set 3272 and 3273 is used instead.
Refer to Section Auto-tuning of Chapter Operating the Control for warnings associated
with this function.
Parameter Assignment/Addressing
6.9 Options for Stability Menu (3) - second half
Control Manual
134
Operating Manual, A5E50491925A
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......