Prerequisites to initiating pre-charge types 5 or 6
• The
DriveReadyToPrecharge
flag in the lower right corner must be set true for pre-
charge to begin. Monitor the progress on the ‘MedVolts’, ‘Precharge State’, and
‘PrechargeExitState’ variables on the right side. Every step in the pre-charge sequence is
logged in the event log, including any fault conditions that abort pre-charge. Also the exit
condition from the pre-charge state machine is logged.
• If all conditions are met, the
DriveReadyToPrecharge_I
flag is true. If any conditions
are not met, the flag is set false, therefore this flag can be used as part of the conditions to
start pre-charge. Pre-charge cannot be initialized or started if this flag is not true. Once pre-
charge commences, the flag goes false and remains false until all conditions are again met.
• When all conditions are met, the pre-charge state machine advances from the initial state of
"
PRECHARGE_FAULTED
" through
"
INIT_PRECHARGE2
", into the "
PRECHARGE_READY
"
state. The loss of the
DriveReadyToPrecharge_I
flag causes the state machine to cycle
back to "
INIT_PRECHARGE2
" until the drive is ready.
– Type 5 or 6 pre-charge selected
– Drive not running
– MV is low (not OK)
– Output to M1 Permissive is open,
DO-2d – P14 – TIMV
– Output to close M1 is open,
DO-1c – P9 – CIMV
– M1 is open,
M1 Close Ack – DI-2e – P18
– M2 is open,
M2 Close Ack – DI-3d – P15
– M3 is open,
M3 Close Ack – DI-0e – P16
– M4 is open,
M4 Close Ack – DI-1e – P17
– No medium low fault
– LFR not tripped and latched (due to Input Protection) or dedicated input protection isn't
used
– No pre-charge fault exists
– MV is not disabled,
MainInputVoltageDisable_O
is false, or maintenance or service
mode is enabled.
– No pre-charge circuit breaker alarm active
– No pre-charge contactor alarm active
– No pre-charge main contactor fault
Advanced Operating Functions
8.19 Pre-charge using Dedicated I/O
Control Manual
Operating Manual, A5E50491925A
303
Summary of Contents for SINAMICS PERFECT HARMONY GH180
Page 2: ......
Page 22: ...Table of contents NXGPro Control Manual 20 Operating Manual A5E50491925A ...
Page 24: ...Security NXGPro Control Manual 22 Operating Manual A5E50491925A ...
Page 504: ...NEMA Table NXGPro Control Manual 502 Operating Manual A5E50491925A ...
Page 517: ...Index D NXGPro Control Manual Operating Manual A5E50491925A 515 ...
Page 518: ...Index NXGPro Control Manual 516 Operating Manual A5E50491925A ...
Page 530: ...Glossary NXGPro Control Manual 528 Operating Manual A5E50491925A ...
Page 537: ......